Assessing building performance in use 3: energy performance of the Probe buildings

被引:159
作者
Bordass, B
Cohen, R
Standeven, M
Leaman, A
机构
[1] William Bordass Associates, London NW1 8JJ, England
[2] Energy Sustainable Dev, Overmoor Farm, Corsham SN13 9TZ, Wilts, England
[3] Bldg Use Studies Ltd, London W1P 3PA, England
关键词
benchmarks; carbon dioxide emissions; energy consumption; metering; post-occupancy surveys; sustainability; unintended consequences; United Kingdom;
D O I
10.1080/09613210010008036
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
By early 1999, the Probe series of post-occupancy studies had reported individually on 16 buildings. This paper compares their energy performance and carbon emissions (for technical performance and occupant satisfaction, see papers 2 and 4 in this issue). All but one building (which paradoxically used the least energy of Probe's air-conditioned offices) claimed to be energy efficient, but achieved performance ranged from excellent to below average. Across the sample, there was a factor of six in carbon dioxide emissions per unit floor area, and even more per occupant. The air-conditioned buildings tended to use the most energy: they usually contained more equipment, were more intensively occupied, but also usually ran more liberally and wastefully - as did more complex systems generally. Often complication seemed to have been added before the fundamentals had been made efficient. Design objectives were also frustrated by poor airtightness, control problems, unintended consequences, a dearth of energy management, and a tendency for systems to default to 'on' - also a pathological trend for information technology and its associated cooling demands. Solutions include load reduction, 'gentle engineering', better matches between demand and supply, and predictions based on a better understanding of in-use performance.
引用
收藏
页码:114 / 128
页数:15
相关论文
共 15 条
[1]  
*ARUP R D, 1992, PASS SOL MEAS AIR CO
[2]   Assessing building performance in use 2: technical performance of the Probe buildings [J].
Bordass, B ;
Cohen, R ;
Standeven, M ;
Leaman, A .
BUILDING RESEARCH AND INFORMATION, 2001, 29 (02) :103-113
[3]   Assessing building performance in use 5: conclusions and implications [J].
Bordass, B ;
Leaman, A ;
Ruyssevelt, P .
BUILDING RESEARCH AND INFORMATION, 2001, 29 (02) :144-157
[4]  
*CIBSE, 1999, 22 CIBSE
[5]   Assessing building performance in use 1: the Probe process [J].
Cohen, R ;
Standeven, M ;
Bordass, B ;
Leaman, A .
BUILDING RESEARCH AND INFORMATION, 2001, 29 (02) :85-102
[6]   The Green Building Challenge in the UK [J].
Curwell, S ;
Yates, A ;
Howard, N ;
Bordass, B ;
Doggart, J .
BUILDING RESEARCH AND INFORMATION, 1999, 27 (4-5) :286-293
[7]  
*DETR, 1998, 106 DETR BRECSU EN E
[8]  
*DETR, 1991, 21 DETR BRECSU
[9]  
*DETR, 1993, EN CONS GUID
[10]  
*DETR, 2000, EN CONS GUID, V19