Assessing building performance in use 2: technical performance of the Probe buildings

被引:71
作者
Bordass, B
Cohen, R
Standeven, M
Leaman, A
机构
[1] William Bordass Associates, London NW1 8JJ, England
[2] Energy Sustainable Dev, Overmoor Farm, Corsham SN13 9TZ, Wilts, England
[3] Bldg Use Studies Ltd, London W1P 3PA, England
关键词
advanced natural ventilation; buildings; control systems; HVAC systems; lighting; performance; post-occupancy surveys; thermal capacity; usability; window design; UK;
D O I
10.1080/09613210010008027
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
From 1995-1999, the Probe series of post-occupancy studies reported individually on the performance of 16 buildings. This paper introduces the buildings - seven office, five educational and four other - and reviews aspects of their technical performance in a number of areas: building envelope and window design, heating, hot water and ventilation systems, artificial lighting, controls and operations and ICT (the energy and occupant surveys are reported in papers 3 and 4 of this series). The buildings are above average in performance for the UK - some exceptionally so - but nevertheless certain types of problem were widespread. Many buildings had poor airtightness and problems with controls, which sometimes seriously reduced occupant satisfaction and energy efficiency (which is discussed in more detail in paper 3). Important lessons for designers, owners, tenants and operators of buildings are described, based on feedback from Probe. For both old and new techniques and technologies there are frequently chronic, minor problems; often revealing the need to make components, systems and particularly their means of control more understandable to those using and operating them; to avoid unnecessary complication; for design to be appropriate to the management resources likely to be available to run the buildings; and for all but the simplest and most standardized buildings to have a period of 'sea trials' following completion in which performance is evaluated, problems fixed, and information collected for the benefit of the organizations concerned and of the whole industry.
引用
收藏
页码:103 / 113
页数:11
相关论文
共 12 条
[1]   Assessing building performance in use 3: energy performance of the Probe buildings [J].
Bordass, B ;
Cohen, R ;
Standeven, M ;
Leaman, A .
BUILDING RESEARCH AND INFORMATION, 2001, 29 (02) :114-128
[2]   Assessing building performance in use 5: conclusions and implications [J].
Bordass, B ;
Leaman, A ;
Ruyssevelt, P .
BUILDING RESEARCH AND INFORMATION, 2001, 29 (02) :144-157
[3]  
*CIBSE, 2000, APPL MAN, V13
[4]   Assessing building performance in use 1: the Probe process [J].
Cohen, R ;
Standeven, M ;
Bordass, B ;
Leaman, A .
BUILDING RESEARCH AND INFORMATION, 2001, 29 (02) :85-102
[5]  
*CONSTR TASK FORC, 1998, RETH CONSTR EG REP
[6]  
*DETR, 1991, 20 DETR BRECSU
[7]  
EVANS B, 1992, ARCHITECTS J, P38
[8]   Assessing building performance in use 4: the Probe occupant surveys and their implications [J].
Leaman, A ;
Bordass, B .
BUILDING RESEARCH AND INFORMATION, 2001, 29 (02) :129-143
[9]  
POTTER IN, 1995, 895 BSRIA
[10]  
ROWE DM, 1997, MIXED MODE THERMAL C