Low and high voltage ride-through of DFIG wind turbines using hybrid current controlled converters

被引:93
作者
Mohseni, Mansour [1 ]
Masoum, Mohammad A. S. [1 ]
Islam, Syed M. [1 ]
机构
[1] Curtin Univ Technol, Dept Elect & Comp Engn, Perth, WA, Australia
关键词
Voltage sag ride-through; Voltage swell ride-through; DFIG-based wind turbines; Hybrid current controller; FED INDUCTION GENERATOR; PWM CONVERTERS; OPERATION; MODEL;
D O I
10.1016/j.epsr.2011.02.010
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Doubly fed induction generators have been recognized as the dominant technology used in wind generation systems. However, this type of wind generator is very sensitive to the drop/rise in the supply voltage and without efficient "ride-through" strategy, continuous operation of DFIG may fail due to destructive overcurrents in the rotor winding or large overvoltages in the dc-link capacitor. This paper introduces a hybrid current control scheme, implemented in the rotor-side and grid-side converters of DFIG, to enhance low and high voltage ride-through capacities of DFIG-based wind turbines. The proposed control scheme is constituted of two switching strategies integrated with a supervisory control unit: standard PI current controllers for normal operating conditions and vector-based hysteresis current controllers for DFIG protection during severe voltage sag/swell conditions. Time-domain simulation studies are carried Out to examine the effectiveness of the proposed ride-through strategy under various types of grid disturbances. It is shown that the proposed controller constrains the rotor current and dc-link voltage within the safety limits of DFIG and as a result, the wind generator can comply with the strict low/high voltage ride-through requirements stipulated by modern grid codes. (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:1456 / 1465
页数:10
相关论文
共 32 条
[1]  
AEMC, 2010, NAT EL RUL VERS 39
[2]  
[Anonymous], IEEE T POWE IN PRESS
[3]   A Review of the State of the Art of Power Electronics for Wind Turbines [J].
Chen, Zhe ;
Guerrero, Josep M. ;
Blaabjerg, Frede .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2009, 24 (08) :1859-1875
[4]  
FELTES C, 2008, POW EN SOC GEN M CON, P1, DOI DOI 10.1109/PES.2008.4596803
[5]   A fault tolerant doubly fed induction generator wind turbine using a parallel grid side rectifier and series grid side converter [J].
Flannery, Patrick S. ;
Venkataramanan, Giri .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2008, 23 (03) :1126-1135
[6]   Ride-Through Control of a Doubly Fed Induction Generator Under Unbalanced Voltage Sags [J].
Gomis-Bellmunt, Oriol ;
Junyent-Ferre, Adria ;
Sumper, Andreas ;
Bergas-Jane, Joan .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2008, 23 (04) :1036-1045
[7]   Model-based current control of AC machines using the internal model control method [J].
Harnefors, L ;
Nee, HP .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1998, 34 (01) :133-141
[8]   Power conditioner control and protection for distributed generator's and storage [J].
Hatziadoniu, CJ ;
Nikolov, EN ;
Pourboghrat, F .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2003, 18 (01) :83-90
[9]  
HUA J, 2010, ELECTR POW SYST RES, V80, P847
[10]   Operation of a voltage source converter at increased utility voltage [J].
Kaura, V ;
Blasko, V .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 1997, 12 (01) :132-137