Estimation of the maximum heat flux in the inverted meniscus type evaporator of a flat miniature heat pipet

被引:26
作者
Khrustalev, D [1 ]
Faghri, A [1 ]
机构
[1] UNIV CONNECTICUT,DEPT MECH ENGN,STORRS,CT 06269
关键词
Condensation - Estimation - Evaporators - Flow of fluids - Heat pipes - Porous materials - Surface tension - Thin films - Vapors;
D O I
10.1016/0017-9310(95)00270-7
中图分类号
O414.1 [热力学];
学科分类号
摘要
A new flat miniature heat pipe configuration for application to cooling electronic components is proposed for high heat fluxes (over 100 W cm(-2)) on the evaporator wail. The heat pipe contains the inverted meniscus type evaporator and axial capillary grooves covered with a porous plate for the liquid transport. Numerical results for the capillary limit and maximum heat flux, which has been calculated with respect to the formation of the vapor blanket in the porous structure of the evaporator, are presented for a copper-water miniature heat pipe with the external dimensions 2 x 7 x 120 mm.
引用
收藏
页码:1899 / 1909
页数:11
相关论文
共 17 条
[11]  
Nield D.A., 1992, Convection in porous media
[12]   COMPILATION OF EVAPORATION COEFFICIENTS [J].
PAUL, B .
ARS JOURNAL, 1962, 32 (09) :1321-1328
[13]   EVAPORATION FROM A POROUS FLOW CONTROL ELEMENT ON A POROUS HEAT SOURCE [J].
RAIFF, RJ ;
WAYNER, PC .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1973, 16 (10) :1919-1929
[14]  
SHAH RK, 1987, HDB SINGLE PHASE CON
[15]  
SOLOVEV SL, 1987, P 6 INT HEAT PIP C G, V1, P116
[16]  
STEPANOV VG, 1977, J ENG PHYSICS THERMO, V32, P1000
[17]  
WULZ H, 1990, P AIAA ASME 5 JOINT