Multivariable Servomechanism Controller for Autonomous Operation of a Distributed Generation Unit: Design and Performance Evaluation

被引:126
作者
Karimi, Houshang [1 ]
Davison, Edward J. [2 ]
Iravani, Reza [2 ]
机构
[1] Sharif Univ Technol, Dept Elect Engn, Tehran 113659363, Iran
[2] Univ Toronto, Dept Elect & Comp Engn, Toronto, ON M5S 3G4, Canada
关键词
Distributed energy resource; distributed generation; islanded operation; microgrid; multivariable control; robust servomechanism problem; INVERTERS; STRATEGIES; SUBSEQUENT; CONVERTER;
D O I
10.1109/TPWRS.2009.2031441
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A linear time-invariant (LTI) robust servomechanism controller for islanded (autonomous) operation of a distributed generation (DG) unit and its local load is proposed. The DG unit utilizes a voltage-sourced converter (VSC) as the interface medium. The controller design is obtained by introducing a new optimal controller design procedure, in conjunction with a proposed non-conservative robustness constraint. The proposed controller utilizes 1) an internal oscillator for frequency control and 2) a robust servomechanism controller (RSC) to regulate the island voltage. Despite uncertainty of the load parameters, the proposed controller guarantees robust stability and pre-specified performance criteria, e. g., fast transient response and zero steady-state error. The theoretical aspects of the proposed robust servomechanism controller including the existence conditions, design of the controller, and robust stability analysis of the closed-loop system are studied. Moreover, the performance of the robust servomechanism controller based on 1) simulation studies in the MATLAB software environment, and 2) experiments in a laboratory-scale setup, is presented in this paper. In particular, reference signal tracking and robustness of the closed-loop system with respect to the load parameter uncertainty are investigated. Both computer simulation studies and experimental results confirm that the proposed robust controller provides the specified performance characteristics of the closed-loop system.
引用
收藏
页码:853 / 865
页数:13
相关论文
共 40 条
[21]  
Illindala M. S., 2004, NAT RENEWABLE ENERGY
[22]   Control of an electronically-coupled distributed resource unit subsequent to an islanding event [J].
Karimi, Houshang ;
Nikkhajoei, Hassan ;
Iravani, Reza .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (01) :493-501
[23]   Power management strategies for a microgrid with multiple distributed generation units [J].
Katiraei, F. ;
Iravani, M. R. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (04) :1821-1831
[24]   Micro-grid autonomous operation during and subsequent to islanding process [J].
Katiraei, F ;
Iravani, AR ;
Lehn, PW .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) :248-257
[25]  
Krishnamurthy S., 2009, Control of wound field synchronous machine gen-sets for operation in a CERTS microgrid
[26]  
LI Q, 1986, P IEEE CONTR DEC C A, P751
[27]  
LI Y, 2005, P IEEE IND APPL C 40, V4, P2441
[28]   Defining control strategies for microgrids islanded operation [J].
Lopes, JAP ;
Moreira, CL ;
Madureira, AG .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (02) :916-924
[29]   A LOOP SHAPING DESIGN PROCEDURE USING H-INFINITY-SYNTHESIS [J].
MCFARLANE, D ;
GLOVER, K .
IEEE TRANSACTIONS ON AUTOMATIC CONTROL, 1992, 37 (06) :759-769
[30]   Distributed Generation Interface to the CERTS Microgrid [J].
Nikkhajoei, Hassan ;
Lasseter, Robert H. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) :1598-1608