Semi-empirical modelling of a variable speed scroll compressor with vapour injection

被引:40
作者
Dardenne, Laurent [1 ]
Fraccari, Enrico [2 ]
Maggioni, Alessandro [3 ]
Molinaroli, Luca [3 ]
Proserpio, Luca [3 ]
Winandy, Eric [1 ]
机构
[1] Emerson Climate Technol, B-4840 Welkenraedt, Belgium
[2] Emerson Climate Technol, D-52076 Aachen, Germany
[3] Politecn Milan, Dipartimento Energia, I-20156 Milan, Italy
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2015年 / 54卷
关键词
Modelling; Scroll compressor; Vapour injection; Variable speed; HEAT-PUMP SYSTEM; REFRIGERANT INJECTION; COLD REGIONS; PERFORMANCE; R410A; CYCLES;
D O I
10.1016/j.ijrefrig.2015.03.004
中图分类号
O414.1 [热力学];
学科分类号
摘要
Vapour injection scroll compressors are nowadays gaining attention in vapour compression systems, especially in high temperature lift application, due to the advantages they provide. To date, proposed models of this kind of compressor are mainly deterministic models, requiring a detailed description of compressor geometry and allowing, in turn, minute calculation of the refrigerant state as function of orbiting angle. Semi-empirical models are largely proposed for standard scroll compressors in order to accurately compute compressor performance without the need of the knowledge of compressor geometrical feature. In this paper, a semi-empirical model of a variable speed scroll compressor with vapour injection is introduced and validated over a set of 63 experimental data finding that 89%-98% of calculated suction and injection refrigerant mass flow rates, compressor electrical power and refrigerant temperature at compressor discharge agree within +/- 5%, +/- 10% or +/- 5 K with respect to the experimental values. (C) 2015 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:76 / 87
页数:12
相关论文
共 28 条
[1]  
[Anonymous], 2003, 13771 EN
[2]   Scroll compressor modelling for heat pumps using hydrocarbons as refrigerants [J].
Byrne, Paul ;
Ghoubali, Redouane ;
Miriel, Jacques .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 41 :1-13
[3]   Optimization of injection holes in symmetric and asymmetric scroll compressors with vapor injection [J].
Cho, Il Yong ;
Ko, Suk Bin ;
Kim, Yongchan .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (04) :850-860
[4]  
Creux L, 1905, US, Patent No. [US801182A[P], 801182]
[5]   Characterization of a scroll compressor under extended operating conditions [J].
Cuevas, Cristian ;
Lebrun, Jean ;
Lemort, Vincent ;
Winandy, Eric .
APPLIED THERMAL ENGINEERING, 2010, 30 (6-7) :605-615
[6]   Modelling the performance of a scroll expander for small organic Rankine cycles when changing the working fluid [J].
Giuffrida, Antonio .
APPLIED THERMAL ENGINEERING, 2014, 70 (01) :1040-1049
[7]   Optimum cycle control of a two-stage injection heat pump with a double expansion sub-cooler [J].
Heo, Jaehyeok ;
Kang, Hoon ;
Kim, Yongchan .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2012, 35 (01) :58-67
[8]   Comparison of the heating performance of air-source heat pumps using various types of refrigerant injection [J].
Heo, Jaehyeok ;
Jeong, Min Woo ;
Baek, Changhyun ;
Kim, Yongchan .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (02) :444-453
[9]  
Joppolo CM, 2010, ASHRAE TRAN, V116, P310
[10]  
Lemmon E, 2013, NIST reference fluid thermodynamic and transport properties database: REFPROP version 9.1, V23