Load estimation for load monitoring at distribution substations

被引:32
作者
Baran, ME [1 ]
Freeman, LAA
Hanson, F
Ayers, V
机构
[1] N Carolina State Univ, Raleigh, NC 27695 USA
[2] NCEMC, Raleigh, NC 27616 USA
关键词
load estimation; power distribution; power system monitoring;
D O I
10.1109/TPWRS.2004.840409
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper addresses the issues related to the real-time monitoring of loads at distribution substations. A method is proposed for estimating the measurements that becomes unavailable due to metering problems. To address the low redundancy associated with the load monitoring scheme, the method uses a regression-based model and makes use of the strong correlation between the loads that are geographically close to each other. The method was tested with actual field data. The results indicate that the method has the acceptable performance for measurement loss of up to a week. The average estimation error varies 2-7.5%, depending on which measurement is lost and how up-to-date the historical data is.
引用
收藏
页码:164 / 170
页数:7
相关论文
共 13 条
[11]  
SAKR MM, 1989, P I ELECT ENG C JAN, P15
[12]  
SARGENT A, 1994, IEEE T POWER SYST, V9, P145
[13]  
Walpole RE., 1993, Probability and Statistics for Engineers and Scientists