Experimental study on a continuous adsorption water chiller with novel design

被引:100
作者
Liu, YL [1 ]
Wang, RZ [1 ]
Xia, ZZ [1 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200030, Peoples R China
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2005年 / 28卷 / 02期
关键词
design; adsorption system; water chiller; water; silica gel; experiment; performance; COP;
D O I
10.1016/j.ijrefrig.2004.09.004
中图分类号
O414.1 [热力学];
学科分类号
摘要
A newly developed adsorption water chiller is introduced and tested. In the new adsorption refrigeration system, there are no refrigerant valves, the problem of mass transfer resistance resulting in pressure drop along refrigerant passage in conventional systems when methanol or water is used as refrigerant can be absolutely solved. Silica-gel-water is used as working pair and mass recovery-like process is adopted in order to use low temperature heat source ranging from 70 to 85 degreesC effectively. The experiment results demonstrate that the chiller (26.4 kg silica-gel in each adsorber) has a cooling capacity of 2-7.3 kW and COP ranging 0.2-0.42 according to different evaporating temperatures. Based on the experimental tests of the first prototype, the second prototype is designed and tested; the experimental data demonstrate that the chiller performance has been greatly improved, with a heat source temperature of 80 degreesC, a COP over 0.5 and cooling capacity of 9 kW has been achieved at evaporating temperature of 13 T. (C) 2004 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:218 / 230
页数:13
相关论文
共 15 条
[1]   Mass recovery adsorption refrigeration cycle-improving cooling capacity [J].
Akahira, A ;
Alam, KCA ;
Hamamoto, Y ;
Akisawa, A ;
Kashiwagi, T .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (03) :225-234
[2]  
Boelman EC, 1997, ASHRAE TRAN, V103, P139
[3]  
Boelman EC, 1995, ASHRAE TRAN, V101, P358
[4]   MODELING OF A SILICA-GEL WATER-ADSORPTION COOLING SYSTEM [J].
CHO, SH ;
KIM, JN .
ENERGY, 1992, 17 (09) :829-839
[5]   Simulation of a continuous multiple-bed regenerative adsorption cycle [J].
Critoph, RE .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2001, 24 (05) :428-437
[6]  
Okumura S, 1991, Method of operating adsorption refrigerator, Patent No. 5024064
[7]   Waste heat driven dual-mode, multi-stage, multi-bed regenerative adsorption system [J].
Saha, BB ;
Koyama, S ;
Kashiwagi, T ;
Akisawa, A ;
Ng, KC ;
Chua, HT .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2003, 26 (07) :749-757
[8]   Solar/waste heat driven two-stage adsorption chiller: the prototype [J].
Saha, BB ;
Akisawa, A ;
Kashiwagi, T .
RENEWABLE ENERGY, 2001, 23 (01) :93-101
[9]  
Saha BB, 1995, ASHRAE TRAN, V101, P348
[10]  
SAHA BB, 1997, ASHRAE T RES, P51