Phase selection based on superimposed components

被引:20
作者
Thomas, DWP
Jones, MS
Christopoulos, C
机构
[1] Department of Electrical and Electronic Engineering, Nottingham NG7 2RD, University Park
[2] GEC Alsthom T and D Protection and Control Ltd., St Leonards Works
关键词
phase selection; superimposed voltages; distance protection; fault conditions;
D O I
10.1049/ip-gtd:19960292
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A method is described for faulted phase selection for non-unit-distance protection using the superimposed voltages and currents initiated by faults. Even though superimposed voltages and currents are comprised of many incident and reflected waves it is shown for the first time that the criteria used for phase selection remain valid throughout the fault period. The proposed method is hence very powerful. To demonstrate the potential of the scheme, its response to a number of fault conditions is presented.
引用
收藏
页码:295 / 299
页数:5
相关论文
共 10 条
[1]   EFFECTS OF FREQUENCY-DEPENDENCE AND LINE PARAMETERS ON SINGLE ENDED TRAVELING-WAVE BASED FAULT LOCATION SCHEMES [J].
ANCELL, GB ;
PAHALAWATHTHA, NC .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1992, 139 (04) :332-342
[2]  
BERNARD P, 1982, IEEE T PAS, V101, P491
[3]  
BOLLEN MHJ, 1989, P 4 INT C DEV POW SY, P135
[4]   3 TERMINAL LINE PROTECTION BASED ON A SUPERIMPOSED COMPONENT IMPEDANCE RELAY [J].
DANIEL, JS ;
AGGARWAL, RK ;
JOHNS, AT .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1993, 140 (06) :447-454
[5]   NEW APPROACH TO ULTRA-HIGH-SPEED PHASE SELECTION IN SINGLE-POLE AUTORECLOSURE SCHEMES [J].
JOHNS, AT ;
MAHMOUD, MME .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1986, 133 (04) :188-200
[6]  
JOHNS AT, 1988, IEE P C, V135, P335
[7]  
MEYER WS, EMTP RULE BOOK
[8]  
THOMAS DWP, 1990, THESIS U NOTTINGHAM
[9]  
Wedepohl L. M., 1964, P I ELECT ENG, V111, P2051
[10]  
WEDEPOHL LM, 1963, P I ELECTR ENG, V110, P2200, DOI DOI 10.1049/PIEE.1963.0314