Stiction - definition, modelling, detection and quantification

被引:89
作者
Choudhury, M. A. A. Shoukat [2 ]
Jain, Mridul [1 ]
Shah, Sirish L. [1 ]
机构
[1] Univ Alberta, Dept Chem & Mat Engn, Edmonton, AB T6G 2G6, Canada
[2] Bangladesh Univ Engn & Technol, Dept Chem Engn, Dhaka 1000, Bangladesh
关键词
stiction; deadband; control valve; controller performance monitoring;
D O I
10.1016/j.jprocont.2007.07.004
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Stiction or high static friction is a common problem in spring-diaphragm type control valves, which are widely used in the process industry. Recently, there have been many attempts to understand, define, model and detect stiction in control valves. There are several methods for detecting stiction, but quantification of the actual amount of stiction still remains a challenge. This paper discusses briefly the definition and modelling of stiction. Then it demonstrates a new method to detect and quantify the actual amount of valve stiction using routine operating data. The proposed method is completely data-driven. No additional excitation or experimentation of the plant is required. (c) 2007 Elsevier Ltd. All rights reserved.
引用
收藏
页码:232 / 243
页数:12
相关论文
共 18 条
[11]   A simple method for detection of stiction in control valves [J].
Horch, A .
CONTROL ENGINEERING PRACTICE, 1999, 7 (10) :1221-1231
[12]  
MARTIN GD, 1991, HYDROCARB PROCESS, V70, P68
[13]  
SINGHAL A, 2005, J PROCESS CONTR, V15, P71382
[14]   Control loop performance assessment. 1. A qualitative approach for stiction diagnosis [J].
Srinivasan, R ;
Rengaswamy, R ;
Miller, R .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2005, 44 (17) :6708-6718
[15]   Control loop performance assessment. 2. Hammerstein model approach for stiction diagnosis [J].
Srinivasan, R ;
Rengaswamy, R ;
Narasimhan, S ;
Miller, R .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2005, 44 (17) :6719-6728
[16]   A segmentation-based method for detection of stiction in control valves [J].
Stenman, A ;
Gustafsson, F ;
Forsman, K .
INTERNATIONAL JOURNAL OF ADAPTIVE CONTROL AND SIGNAL PROCESSING, 2003, 17 (7-9) :625-634
[17]   An automatic method for detection of valve stiction in process control loops [J].
Yamashita, Y .
CONTROL ENGINEERING PRACTICE, 2006, 14 (05) :503-510
[18]  