Zoned vertical ultraclean operating room ventilation - A novel concept making long side walls unnecessary

被引:20
作者
Friberg, BEE [1 ]
Friberg, S [1 ]
Burman, LG [1 ]
机构
[1] SWEDISH INST INFECT DIS CONTROL,S-10521 STOCKHOLM,SWEDEN
来源
ACTA ORTHOPAEDICA SCANDINAVICA | 1996年 / 67卷 / 06期
关键词
D O I
10.3109/17453679608997760
中图分类号
R826.8 [整形外科学]; R782.2 [口腔颌面部整形外科学]; R726.2 [小儿整形外科学]; R62 [整形外科学(修复外科学)];
学科分类号
摘要
We evaluated a novel concept of High Efficiency Particulate Air (HEPA)-filtered vertical Laminar Air Flow (LAF) for operating room ventilation, designed to be used without side-walls. The LAF-unit has a central zone with an airflow of 0.4 m/s and a peripheral zone with an airflow of 0.2 m/s. The design provides an exponential downflow of air resembling an upside-down trumpet mouth and it was claimed to prevent entrainment of peripheral contaminated air. The unit was evaluated with regard to elimination of particles with focus on bacteria-carrying particles (colony-forming units = cfu) during rigidly standardized sham operations. Three different lengths of walls/enclosures (short-ending 2.0 m, medium 1.0 m and long 0.2 m above the floor) were tested. It provided a high degree of bacteriological cleanliness (0.05-4 cfu/m(3) of air and 7-64 cfu/m(2)/h surface contamination) and its efficiency was proved to be independent of the length of the enclosures. We conclude that the novel zoned ultraclean vertical LAF unit is versatile, as it allows for omitting long side-walls, without compromising bacteriological safety.
引用
收藏
页码:578 / 582
页数:5
相关论文
共 14 条
[1]   AIR CONTAMINATION DURING HIP AND KNEE ARTHROPLASTIES - HORIZONTAL LAMINAR-FLOW RANDOMIZED VS CONVENTIONAL VENTILATION [J].
AHL, T ;
DALEN, N ;
JORBECK, H ;
HOBORN, J .
ACTA ORTHOPAEDICA SCANDINAVICA, 1995, 66 (01) :17-20
[2]   STERILE-AIR OPERATING THEATRE ENCLOSURE [J].
CHARNLEY, J .
BRITISH JOURNAL OF SURGERY, 1964, 51 (03) :195-&
[3]   Inefficiency of upward displacement operating theatre ventilation [J].
Friberg, B ;
Friberg, S ;
Burman, LG ;
Lundholm, R ;
Ostensson, R .
JOURNAL OF HOSPITAL INFECTION, 1996, 33 (04) :263-272
[4]  
FRIBERG B, 1980, ACTA ORTHOP SCAND, V51, P376
[5]  
FRIBERG B, 1994, ACTA ORTHOP SCA S260, V65, P71
[6]  
HAERI GB, 1980, CLIN ORTHOP RELAT R, V148, P160
[7]   AEROBIOLOGY IN THE OPERATING-ROOM - A REVIEW [J].
HAMBRAEUS, A .
JOURNAL OF HOSPITAL INFECTION, 1988, 11 :68-76
[8]  
HILLERBRANT B, 1990, SWISS CONTAMINATIO A, V4, P336
[9]  
HOWORTH FH, 1985, LANCET, P386
[10]   AIRBORNE CONTAMINATION OF WOUNDS IN JOINT REPLACEMENT OPERATIONS - THE RELATIONSHIP TO SEPSIS RATES [J].
LIDWELL, OM ;
LOWBURY, EJL ;
WHYTE, W ;
BLOWERS, R ;
STANLEY, SJ ;
LOWE, D .
JOURNAL OF HOSPITAL INFECTION, 1983, 4 (02) :111-131