A unified geometric approach to process and sensor fault identification and reconstruction: The unidimensional fault case

被引:74
作者
Dunia, R
Qin, SJ [1 ]
机构
[1] Univ Texas, Dept Chem Engn, Austin, TX 78712 USA
[2] Fisher Rosemount Syst, Austin, TX 78754 USA
关键词
process monitoring; principal component analysis; fault detection; fault identification; measurement reconstruction;
D O I
10.1016/S0098-1354(97)00277-9
中图分类号
TP39 [计算机的应用];
学科分类号
081203 ; 0835 ;
摘要
Fault detection and process monitoring using principal component analysis (PCA) have been studied intensively and applied to industrial processes. This paper addresses some fundamental issues in detecting and identifying faults. We give conditions for detectability, reconstructability, and identifiability of faults described by fault direction vectors. Such vectors can represent process as well as sensor faults using a unified geometric approach. Measurement reconstruction is used for fault identification, and consists of sliding the sample vector towards the PCA model along the fault direction. An unreconstructed variance is defined and used to determine the number of principal components for best fault identification and reconstruction. The proposed approach is demonstrated with data from a simulated process plant. Future directions on how to incorporate dynamics and multidimensional faults are discussed. (C) 1998 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:927 / 943
页数:17
相关论文