Optimization of Photovoltaic Penetration in Distribution Systems Considering Annual Duration Curve of Solar Irradiation

被引:75
作者
Lin, Chia-Hung [1 ]
Hsieh, Wei-Lin [1 ]
Chen, Chao-Shun [2 ,3 ]
Hsu, Cheng-Ting [4 ]
Ku, Te-Tien [3 ]
机构
[1] Natl Kaohsiung Univ Appl Sci, Dept Elect Engn, Kaohsiung 807, Taiwan
[2] I Shou Univ, Dept Elect Engn, Kaohsiung 84001, Taiwan
[3] Natl Sun Yat Sen Univ, Dept Elect Engn, Kaohsiung, Taiwan
[4] So Taiwan Univ, Dept Elect Engn, Yung Kang 710, Taiwan
关键词
Net present value; payback year; photovoltaic; ECONOMIC-ANALYSIS; VOLTAGE CONTROL; LOAD SURVEY; GENERATION; PROFITABILITY; ENERGY; COSTS; RISE;
D O I
10.1109/TPWRS.2011.2178619
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The penetration level of a photovoltaic (PV) system is often limited due to the violation of voltage variation introduced by the large intermittent power generation. This paper discusses the use of an active power curtailment strategy to reduce PV power injection during peak solar irradiation to prevent voltage violation so that the PV penetration level of a distribution feeder can be increased to fully utilize solar energy. The PV power generation is simulated according to the hourly solar irradiation and temperature data provided by the weather bureau. The voltage variation at the point of common coupling (PCC) is also derived by executing the 3-load flow analysis to investigate the maximum PV power injection without causing a voltage violation problem. When using the proposed voltage control scheme for limiting PV power injection into the study distribution feeder during high solar irradiation periods, the total power generation and total energy delivered by the PV system over a one-year period are determined according to the annual duration of solar irradiation. The annual cash flow from sales of PV power, the O&M cost over the system life cycle, and the capital investment in the PV system are then used to calculate the payback years and the net present value (NPV) of the PV project. With the proposed voltage control to perform the partial generation rejection of PV systems, the optimal installation capacity of PV systems can be determined by maximizing the net present value of the system so that better cost effectiveness of the PV project and better utilization of solar energy can be obtained.
引用
收藏
页码:1090 / 1097
页数:8
相关论文
共 35 条
  • [31] Coordinated Active Power Curtailment of Grid Connected PV Inverters for Overvoltage Prevention
    Tonkoski, Reinaldo
    Lopes, Luiz A. C.
    El-Fouly, Tarek H. M.
    [J]. IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2011, 2 (02) : 139 - 147
  • [32] Advanced analysis of grid-connected PV system's performance and effect of batteries
    Ueda, Yuzuru
    Kurokawa, Kosuke
    Itou, Takamitsu
    Kitamura, Kiyoyuki
    Akanuma, Katsumi
    Yokota, Masaharu
    Sugihara, Hiroyuki
    Morimoto, Atsushi
    [J]. ELECTRICAL ENGINEERING IN JAPAN, 2008, 164 (01) : 21 - 33
  • [33] Voltage Support Provided by a Droop-Controlled Multifunctional Inverter
    Vasquez, Juan C.
    Mastromauro, R. A.
    Guerrero, Josep M.
    Liserre, Marco
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2009, 56 (11) : 4510 - 4519
  • [34] Analysis of a Commercial Wind Farm in Taiwan Part II: Different Current-Limit Reactors and Load Tap Changers on System Performance
    Wang, Li
    Yeh, Tai-Her
    Lee, Wei-Jen
    Chen, Zhe
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2011, 47 (02) : 954 - 964
  • [35] Integrated high-speed intelligent utility tie unit for disbursed/renewable generation facilities
    Wongsaichua, W
    Lee, WJ
    Oraintara, S
    Kwan, C
    Zhang, F
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2005, 41 (02) : 507 - 513