Estimation of wind penetration as limited by frequency deviation

被引:96
作者
Luo, Changling [1 ]
Far, Hatned Golestani
Banakar, Hadi
Keting, Ping-Kwan
Ooi, Boon-Teck
机构
[1] McGill Univ, Dept Elect & Comp Engn, Montreal, PQ H3A 2A7, Canada
[2] Simsmart Inc, Brossard, PQ J4W 3J9, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
automatic generation control (AGC); Bode diagrams; filter; frequency fluctuation; power fluctuation; speed governors; steam turbines; thermal power plants; transfer function; wind farms; wind power penetration; OPTIMAL ACQUISITION; POWER;
D O I
10.1109/TEC.2006.881082
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
080707 [能源环境工程]; 082001 [油气井工程];
摘要
Wind power fluctuations cause frequency deviation from the 60-Hz standard. Using the composite transfer function G (fw) of a small system of thermal power plants, it is estimated that power fluctuation of 5% of the total thermal plant capacity can be tolerated without exceeding 1% frequency deviation. The technology to filter out the power fluctuations by wind turbine generators for increasing wind power penetration already exists. However, perfect filtering sacrifices as much as 27.6% of the wind power that can otherwise be utilized. The paper presents a method of quantifying wind penetration based on the amount of fluctuating power that can be filtered by wind turbine generators and thermal plants. For optimal wind power acquisition, the penetration level is conservatively estimated to be 50%.
引用
收藏
页码:783 / 791
页数:9
相关论文
共 13 条
[1]
Ackermann T, 2005, WIND POWER IN POWER SYSTEMS, P1, DOI 10.1002/0470012684
[2]
[Anonymous], 1973, IEEE T POWER AP SYST, VPA92, P1904, DOI 10.1109/TPAS.1973.293570
[3]
*HYDR QUEB GROUP, 2002, HYPERSIM 8 9 REF GUI
[4]
*IEEE WORK GROUP, 1991, IEEE T POWER SYST, V2, P753
[5]
Doubly-fed induction generator (DFIG) as a hybrid of asynchronous and synchronous machines [J].
Jiao, LW ;
Ooi, BT ;
Joós, G ;
Zhou, FQ .
ELECTRIC POWER SYSTEMS RESEARCH, 2005, 76 (1-3) :33-37
[6]
KUNDUR P, 1993, POWER SYSTEM STABILI, P617
[7]
Optimal acquisition and aggregation of offshore wind power by multiterminal voltage-source HVDC [J].
Lu, WX ;
Ooi, BT .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (01) :201-206
[8]
Multiterminal LVDC system for optimal acquisition of power in wind-farm using induction generators [J].
Lu, WX ;
Ooi, BT .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2002, 17 (04) :558-563
[9]
LUO C, 2005, THESIS U MCGILL MONT
[10]
Frequency deviation of thermal power plants due to wind farms [J].
Luo, Changling ;
Ooi, Boon-Teck .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2006, 21 (03) :708-716