High-performance voltage control scheme for wind park integration

被引:12
作者
El Moursi, M. [1 ]
Joos, G. [1 ]
Abbey, C. [1 ]
机构
[1] McGill Univ, Dept Elect & Comp Engn, Montreal, PQ H3A 2A7, Canada
关键词
D O I
10.1049/iet-rpg:20060008
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The design and implementation of a new control scheme for reactive power compensation and voltage regulation in the transmission system, as provided and controlled by a wind park is presented. It proposes an optimal tracking secondary voltage control scheme applied to doubly fed induction generator-based wind generators. The ability of the controller to regulate transmission network voltage profiles is demonstrated and compared with primary voltage control, an alternate secondary voltage control approach, and the voltage profile obtained from optimal power flow analysis. The dynamic performance of the controller is also validated in response to system contingencies, namely short circuits. The impact of communication time delays and of the short-circuit ratio on the dynamic performance of the voltage controller are considered. Results show that the controller properly regulates the voltage in steady state and performs properly during transients resulting from short circuits. Decoupling between primary and secondary loops should be applied to mitigate the effects of the time delay.
引用
收藏
页码:151 / 159
页数:9
相关论文
共 19 条
[1]   Co-ordinated voltage control strategy for a doubly-fed induction generator (DFIG)-based wind farm [J].
Cartwright, P ;
Holdsworth, L ;
Ekanayake, JB ;
Jenkins, N .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2004, 151 (04) :495-502
[2]  
CORSI S, 2000, P IEEE PES SUMM M SE, P297
[3]   Control of DFIG wind turbines [J].
Ekanayake, J ;
Holdsworth, L ;
Jenkins, N .
POWER ENGINEER, 2003, 17 (01) :28-32
[4]  
ELMOURSI MS, 2006, P IEEE POW ENG SOC G
[5]  
FARDANESH B, 2002, P IEEE POW ENG SOC W, V1, P640
[6]  
GEHAO S, 2005, P IEEE PES TRANSM DI
[7]   IMPROVED SECONDARY AND NEW TERTIARY VOLTAGE CONTROL [J].
ILIC, MD ;
LIU, XJ ;
LEUNG, G ;
ATHANS, M ;
VIALAS, C ;
PRUVOT, P .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (04) :1851-1862
[8]  
JENNINGS NR, 1997, AGENT TECHNOLOGY FDN
[9]   Emergency voltage control using search and predictive control [J].
Larsson, M ;
Hill, DJ ;
Olsson, G .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2002, 24 (02) :121-130
[10]  
Lefebvre H, 2000, 2000 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-4, P290, DOI 10.1109/PESS.2000.867598