Low-order black-box models for control system design in large power systems

被引:62
作者
Kamwa, I
Trudel, G
GerinLajoie, L
机构
[1] HYDRO QUEBEC,RESEAU TRANSPORT,MONTREAL,PQ H2L 4P5,CANADA
[2] HYDRO QUEBEC,ETUD RESEAUX,MONTREAL,PQ H2L 4P5,CANADA
关键词
small-signal stability; minimal realization; subspace identification reduced-order models; damping controller stabilizer;
D O I
10.1109/59.486110
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
The paper studies two multi-input multi-output (MIMO) procedures for the identification of low-order state-space models of power systems, by probing the network in open loop with low-energy pulses or random signals. Although such data may result from actual measurements, the development assumes simulated responses from a transient stability program, hence benefiting from the existing large base of stability models, While pulse data is processed using the eigensystem realization algorithm, the analysis of random responses is done by means of subspace identification methods. On a prototype Hydro-Quebec power system, including SVCs, DC lines, series compensation, and more than 1100 buses, it is verified that the two approaches are equivalent only when strict requirements are imposed on the pulse length and magnitude. The 10th-order equivalent models derived by random-signal probing allow for effective tuning of decentralized power system stabilizers (PSSs) able to damp both local and very slow inter-area modes.
引用
收藏
页码:303 / 311
页数:9
相关论文
共 25 条
[1]
[Anonymous], 1992, ROBUST CONTROL TOOLB
[2]
BOLLINGER KE, 1995, IEEE T PWRS, V10
[3]
CHO YM, 1994, IEEE T AUTOMAT CONTR, V39, P2004, DOI 10.1109/9.328824
[4]
AN APPROACH TO PSS DESIGN FOR TRANSIENT STABILITY IMPROVEMENT THROUGH SUPPLEMENTARY DAMPING OF THE COMMON LOW-FREQUENCY [J].
GRONDIN, R ;
KAMWA, I ;
SOULIERES, L ;
POTVIN, J ;
CHAMPAGNE, R .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (03) :954-963
[5]
COMPARISON OF PRONY AND EIGENANALYSIS FOR POWER-SYSTEM CONTROL DESIGN [J].
GRUND, CE ;
PASERBA, JJ ;
HAUER, JF ;
NILSSON, S .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (03) :964-971
[6]
GRUND CE, 1989, EIGENANALYSIS FREQUE, P34
[7]
APPLICATION OF PRONY ANALYSIS TO THE DETERMINATION OF MODAL CONTENT AND EQUIVALENT MODELS FOR MEASURED POWER-SYSTEM RESPONSE [J].
HAUER, JF .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1991, 6 (03) :1062-1068
[8]
HSIA TC, 1977, SYSTEM IDENTIFICATIO, pCH4
[9]
AN EIGENSYSTEM REALIZATION-ALGORITHM FOR MODAL PARAMETER-IDENTIFICATION AND MODEL-REDUCTION [J].
JUANG, JN ;
PAPPA, RS .
JOURNAL OF GUIDANCE CONTROL AND DYNAMICS, 1985, 8 (05) :620-627
[10]
A MINIMAL-REALIZATION APPROACH TO REDUCED-ORDER MODELING AND MODAL-ANALYSIS FOR POWER-SYSTEM RESPONSE SIGNALS [J].
KAMWA, I ;
GRONDIN, R ;
DICKINSON, J ;
FORTIN, S .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (03) :1020-1029