Bacterial foraging technique-based optimized active power filter for load compensation

被引:171
作者
Mishra, S. [1 ]
Bhende, C. N. [1 ]
机构
[1] Indian Inst Technol Delhi, Dept Elect Engn, New Delhi 110016, India
关键词
bacterial foraging; power-quality improvement and dynamic behavior of the controller; shunt active power filter;
D O I
10.1109/TPWRD.2006.876651
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The conventional method of obtaining the coefficients of proportional plus integral (PI) controllers for the active power filter utilizes a linear model of the PWM inverter. The values so obtained may not give satisfactory results for a wide variation in operating conditions. This paper presents a new algorithm based on the foraging behavior of E-coli Bacteria in the human intestine, to optimize the coefficients of the PI controller. Through the simulation results, it is observed that the dynamic response of the bacterial foraging PI (BF-PI) controller is quite satisfactory. The proposed BF technique is compared with the genetic algorithm (GA) and found to converge faster than GA to reach the global optimum solution.
引用
收藏
页码:457 / 465
页数:9
相关论文
共 12 条
[11]   Computer-aided modeling and simulation of active power filters [J].
Singh, B ;
Chandra, A ;
Al-Haddad, K .
ELECTRIC MACHINES AND POWER SYSTEMS, 1999, 27 (11) :1227-1241
[12]   NONLINEAR PARAMETER-ESTIMATION VIA THE GENETIC ALGORITHM [J].
YAO, L ;
SETHARES, WA .
IEEE TRANSACTIONS ON SIGNAL PROCESSING, 1994, 42 (04) :927-935