Adaptive diurnal prediction of ambient dry-bulb temperature and solar radiation

被引:23
作者
Ren, MJ [1 ]
Wright, JA
机构
[1] Buro Happold Engn, Manchester, Lancs, England
[2] Dept Civil & Bldg Engn, Loughborough, Leics, England
来源
HVAC&R RESEARCH | 2002年 / 8卷 / 04期
关键词
D O I
10.1080/10789669.2002.10391297
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents a new adaptive weather-prediction model that can be used for on-line control of HVA C and thermal storage systems. The model can predict external dry-bulb temperature and solar radiation over the next 24 h. Because a building with a fabric thermal storage system has a slow response to thermal loads, a predictive controller is essential to operate the building and associated plant installation to respond effectively to external climatic conditions ahead of time. Three prediction methods a e investigated in the paper: a pure stochastic method, a combined deterministic-stochastic method, and an expanded method for short-term temperature forecast. It has been found that the combined deterministic-stochastic method is simpler and gives the smallest prediction errors. For the prediction of solar radiation, a deterministic model is proposed. The proposed prediction algorithms for temperature and radiation are simple and efficient to conduct on a supervisory PC to predict hourly temperature and radiation profiles over the next 24 h. Updating temperature forecasts using observations available with time is also investigated in this paper.
引用
收藏
页码:383 / 401
页数:19
相关论文
共 19 条
  • [1] Athienitis AK, 1988, ASHRAE T, V94, P1050
  • [2] Chen TY, 1996, ASHRAE TRAN, V102, P26
  • [3] Duffie J., 1974, Solar Energy Thermal Processes
  • [4] FERRANO FJ, 1990, ASHRAE TRAN, V96, P723
  • [5] FORRESTER JR, 1984, ASHRAE T, V90, P536
  • [6] HOLST J, 1987, P 3 INT C BUILD EN M, P380
  • [7] STOCHASTIC-ANALYSIS OF BUILDING THERMAL-PROCESSES
    JIANG, Y
    HONG, TZ
    [J]. BUILDING AND ENVIRONMENT, 1993, 28 (04) : 509 - 518
  • [8] Kawashima M, 1995, ASHRAE TRAN, V101, P186
  • [9] Keeney KR, 1997, ASHRAE TRAN, V103, P463
  • [10] Ledolter J, 1983, STAT METHODS FORECAS, DOI [10.1002/9780470316610, DOI 10.1002/9780470316610]