High-quality power generation through distributed control of a power park microgrid

被引:222
作者
Prodanovic, Milan [1 ]
Green, Timothy C. [1 ]
机构
[1] Univ London Imperial Coll Sci & Technol, Dept Elect & Elect Engn, London SW7 2AZ, England
关键词
distributed generation (DG); inverter; microgrid; power quality;
D O I
10.1109/TIE.2006.882019
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Inverters are a necessary interface for several forms of distributed generation (DG) and where they form a microgrid they have the potential to offer high power quality. The challenge is to coordinate the actions of a group of inverters so that they offer the level of power quality known to be possible from fast local control of a single inverter. The case examined here is a power park of several inverter-based DG in relatively close proximity. A basic requirement is that the inverters regulate the grid voltage and share the real and reactive power demands according to their ratings. In small girds with high proportions of nonlinear and unbalanced loads it is also important to actively control the waveform quality in terms of harmonics, transient disturbances, and balance. Further, it is important that these duties are shared equally between the units rather than having one master unit taking the lead in the voltage control function. A constraint faced in designing a sharing system is the limited bandwidth of signal communication even over distances of a few meters. A control method is proposed that separates the control tasks in the frequency domain. Power sharing and voltage regulation are controlled centrally and commands are distributed through a low-bandwidth communication link. Waveform quality functions are controlled in high bandwidth controllers distributed to each local inverter. Experimental tests on a grid of three 10-kVA inverters are used to show that the method fully exploits the inherent fast response of the inverters while also ensuring voltage balance even with extreme load imbalance. It is shown that circulating currents are avoided during steady state and transients.
引用
收藏
页码:1471 / 1482
页数:12
相关论文
共 24 条
[1]  
[Anonymous], IEEE REC PRACT REQ H
[2]  
[Anonymous], 1993, P IECON 93 19 ANN C, DOI DOI 10.1109/IECON.1993.339119
[3]   Control of power electronic interfaces in distributed generation Microgrids [J].
Arulampalam, A ;
Barnes, M ;
Engler, A ;
Goodwin, A ;
Jenkins, N .
INTERNATIONAL JOURNAL OF ELECTRONICS, 2004, 91 (09) :503-523
[4]  
Bollen M.H.J., 2000, Series on Power Engineering
[5]   LOW-THRESHOLD 0.98-MU-M ALUMINUM-FREE STRAINED-QUANTUM-WELL INGAAS/INGAASP/INGAP LASERS [J].
CHANGHASNAIN, CJ ;
BHAT, R ;
LEBLANC, H ;
KOZA, MA .
ELECTRONICS LETTERS, 1993, 29 (01) :1-2
[6]  
Chen JF, 1995, ISIE '95 - PROCEEDINGS OF THE IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS, VOLS 1 AND 2, P237, DOI 10.1109/ISIE.1995.496633
[7]  
Clarke E., 1943, CIRCUIT ANAL AC POWE, V1
[8]   A wireless controller to enhance dynamic performance of parallel inverters in distributed generation systems [J].
Guerrero, JM ;
de Vicuña, LG ;
Matas, J ;
Castilla, M ;
Miret, J .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (05) :1205-1213
[9]  
*IEEE, 2000, SCC21 IEEE
[10]   MICROPROCESSOR-BASED ROBUST DIGITAL-CONTROL FOR UPS WITH 3-PHASE PWM INVERTER [J].
ITO, Y ;
KAWAUCHI, S .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 1995, 10 (02) :196-204