An Improved Design of Current Controller for LCL-Type Grid-Connected Converter to Reduce Negative Effect of PLL in Weak Grid

被引:204
作者
Zhou, Shiying [1 ]
Zou, Xudong [1 ]
Zhu, Donghai [1 ]
Tong, Li [2 ]
Zhao, Yingying [3 ]
Kang, Yong [1 ]
Yuan, Xiaoming [1 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Hubei, Peoples R China
[2] Zhejiang Elect Power Corp Res Inst, Hangzhou 310014, Zhejiang, Peoples R China
[3] State Grid Anhui Econ Res Inst, Hefei 230000, Anhui, Peoples R China
关键词
Current controller; grid-connected converter; phase-locked loop (PLL); small-signal impedance model; weak grid; CONTROL STRATEGY; VECTOR CONTROL; VOLTAGE; STABILITY; INVERTER; FILTERS;
D O I
10.1109/JESTPE.2017.2780918
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
080906 [电磁信息功能材料与结构]; 082806 [农业信息与电气工程];
摘要
For three-phase LCL-type grid-connected converter, when it is attached to weak grid, current control interacts with phase-locked loop (PLL) via point of common coupling voltage. Consequently, PLL dynamic might deteriorate grid current control and even result in system instability. However, the conventional design method of current controller neglects the impact of PLL, and therefore, it is hard for the current controller to mitigate the negative effect of PLL. In this paper, an improved design of current controller, i.e., proportional-integral controller and capacitor-current-feedback active damping, is proposed to reduce the negative effect of PLL on current control. First, a small-signal impedance model is developed to analyze the impact of PLL on current control. Then, the effect of current controller parameters on the converter output impedance is analyzed, and a design guideline to improve the current controller parameters is presented. With the improved parameters, in precondition of satisfying system stability margin under both stiff and weak grid, the negative effect of PLL on current control can be effectively mitigated without employing additional control strategies. Furthermore, the current control has a strong robustness against wide-range variation of grid impedance. Finally, the experiment demonstrates the effectiveness of the proposed design method.
引用
收藏
页码:648 / 663
页数:16
相关论文
共 36 条
[1]
Active Mitigation of Subsynchronous Interactions Between PWM Voltage-Source Converters and Power Networks [J].
Alawasa, Khaled Mohammad ;
Mohamed, Yasser Abdel-Rady Ibrahim ;
Xu, Wilsun .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (01) :121-134
[2]
[Anonymous], 2015, PROC 11 IET INT C AC
[3]
Step-by-Step Controller Design for LCL-Type Grid-Connected Inverter with Capacitor-Current-Feedback Active-Damping [J].
Bao, Chenlei ;
Ruan, Xinbo ;
Wang, Xuehua ;
Li, Weiwei ;
Pan, Donghua ;
Weng, Kailei .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (03) :1239-1253
[4]
Overview of control and grid synchronization for distributed power generation systems [J].
Blaabjerg, Frede ;
Teodorescu, Remus ;
Liserre, Marco ;
Timbus, Adrian V. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (05) :1398-1409
[5]
Adaptive Control of Grid-Connected Inverters Based on Online Grid Impedance Measurements [J].
Cespedes, Mauricio ;
Sun, Jian .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2014, 5 (02) :516-523
[6]
A Time Delay Compensation Method Based on Area Equivalence For Active Damping of an LCL-Type Converter [J].
Chen, Chen ;
Xiong, Jian ;
Wan, Zhiqiang ;
Lei, Ji ;
Zhang, Kai .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2017, 32 (01) :762-772
[7]
Impedance-Phased Dynamic Control Method for Grid-Connected Inverters in a Weak Grid [J].
Chen, Xin ;
Zhang, Yang ;
Wang, Shanshan ;
Chen, Jie ;
Gong, Chunying .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2017, 32 (01) :274-283
[8]
PI State Space Current Control of Grid-Connected PWM Converters With LCL Filters [J].
Dannehl, Joerg ;
Fuchs, Friedrich Wilhelm ;
Thogersen, Paul Bach .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2010, 25 (09) :2320-2330
[9]
Investigation of Active Damping Approaches for PI-Based Current Control of Grid-Connected Pulse Width Modulation Converters With LCL Filters [J].
Dannehl, Joerg ;
Fuchs, Friedrich Wilhelm ;
Hansen, Steffan ;
Thogersen, Paul Bach .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2010, 46 (04) :1509-1517
[10]
Limitations of Voltage-Oriented PI Current Control of Grid-Connected PWM Rectifiers With LCL Filters [J].
Dannehl, Joerg ;
Wessels, Christian ;
Fuchs, Friedrich Wilhelm .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2009, 56 (02) :380-388