Theory and application of distribution electronic power transformer

被引:65
作者
Wang, Dan
Mao, Chengxiong
Lu, Jiming
Fan, Shu
Peng, Fangzheng
机构
[1] Huazhong Univ Sci & Technol, Dept Elect Engn, Wuhan 430074, Peoples R China
[2] Osaka Sangyo Univ, Dept Elect Engn & Elect, Osaka 5748530, Japan
[3] Michigan State Univ, Dept Elect & Comp Engn, E Lansing, MI 48824 USA
关键词
distribution electronic power transformer; distribution system; input/output characteristic; power quality;
D O I
10.1016/j.epsr.2006.02.012
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Three-phase and 4-wire Distribution Electronic Power Transformer's (DEPT's) operation principle is analyzed in this paper. Based on the analysis, the control scheme is established. In this control scheme, the input stage is controlled as a three-phase balanced current source and makes the primary current sinusoidal and power factor easily adjusted. While the output stage is controlled as a three-phase balanced voltage source and keep the load voltage sinusoidal and nominal. In order to meet the requirement of the single phase or unbalanced loads, each phase is an independent voltage source. With the proposed control strategy, the characteristics of DEPT are studied by simulations. And further detailed simulations are carried out to validate the power quality control function of DEPT. The results show that DEPT has very good static and dynamic performances, and it can not only realize the functions of conventional power transformer, but also can prevent from voltage sags, swells, flickers and harmonics infecting the loads while avoid loads impacting the primary system. (C) 2006 Elsevier B.V. All rights reserved.
引用
收藏
页码:219 / 226
页数:8
相关论文
共 12 条
  • [1] Brooks J., 1980, SOLID STATE TRANSFOR
  • [2] *EPRI, 1995, TR105067 EPRI
  • [3] TRANSFORMERLESS 4-WIRE PWM RECTIFIER AND ITS APPLICATION IN AC-DC-AC CONVERTERS
    FRASER, ME
    MANNING, CD
    WELLS, BM
    [J]. IEE PROCEEDINGS-ELECTRIC POWER APPLICATIONS, 1995, 142 (06): : 410 - 416
  • [4] Harada K, 1996, IEEE POWER ELECTRON, P1337, DOI 10.1109/PESC.1996.548755
  • [5] Analysis and design of electronic transformers for electric power distribution system
    Kang, M
    Enjeti, PN
    Pitel, IJ
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 1999, 14 (06) : 1133 - 1141
  • [6] Kassakian J., 1991, Principles of Power Electron
  • [7] Manjrekar MD, 2000, IEEE IND APPLIC SOC, P2496, DOI 10.1109/IAS.2000.883173
  • [8] Marchesoni M, 2002, ISIE 2002: PROCEEDINGS OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS, VOLS 1-4, P1172, DOI 10.1109/ISIE.2002.1025955
  • [9] A power electronic-based distribution transformer
    Ronan, ER
    Sudhoff, SD
    Glover, SR
    Galloway, DL
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (02) : 537 - 543
  • [10] An AC-AC power converter for custom power applications
    Venkataramanan, G
    Johnson, BK
    Sundaram, A
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (03) : 1666 - 1671