A hybrid active filter for damping of harmonic resonance in industrial power systems

被引:145
作者
Fujita, H [1 ]
Yamasaki, T [1 ]
Akagi, H [1 ]
机构
[1] Okayama Univ, Dept Elect Engn, Okayama 7008530, Japan
关键词
active filters; harmonic resonance; power quality; power systems; PWM inverters; voltage harmonics;
D O I
10.1109/63.838093
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a hybrid active filter for damping of harmonic resonance in industrial power systems. The hybrid filter consists of a small-rated active filter and a 5th-tuned passive filter. The active filter is characterized by detecting the 5th-harmonic current flowing into the passive filter. It is controlled in such a way as to behave as a negative or positive resistor by adjusting a feedback gain from a negative to positive value, and vice versa, The negative resistor presented by the active filter cancels a positive resistor inherent in the passive filter, so that the hybrid filter acts as an ideal passive filter with infinite quality factor. This significantly improves damping the harmonic resonance, compared with the passive filter used alone. Moreover, the active filter acts as a positive resistor to prevent an excessive harmonic current from flowing into the passive filter. Experimental results obtained from a 20-kW laboratory model verify the viability and effectiveness of the hybrid active filter proposed in this paper.
引用
收藏
页码:215 / 222
页数:8
相关论文
共 12 条
[1]   New trends in active filters for power conditioning [J].
Akagi, H .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1996, 32 (06) :1312-1322
[2]   Control strategy and site selection of a shunt active filter for damping of harmonic propagation in power distribution systems [J].
Akagi, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) :354-363
[3]   A shunt active filter based on voltage detection for harmonic termination of a radial power distribution line [J].
Akagi, H ;
Fujita, H ;
Wada, K .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1999, 35 (03) :638-645
[4]   Hybrid solutions for improving passive filter performance in high power applications [J].
Bhattacharya, S ;
Cheng, PT ;
Divan, DM .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (03) :732-747
[5]   A PRACTICAL APPROACH TO HARMONIC COMPENSATION IN POWER-SYSTEMS - SERIES CONNECTION OF PASSIVE AND ACTIVE-FILTERS [J].
FUJITA, H ;
AKAGI, H .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1991, 27 (06) :1020-1025
[6]   A shunt active power filter applied to high voltage distribution lines [J].
Hafner, J ;
Aredes, M ;
Heumann, K .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) :266-272
[7]   ACTIVE DAMPING OF RESONANCES IN POWER-SYSTEMS [J].
LE, TN ;
PEREIRA, M ;
RENZ, K ;
VAUPEL, G .
IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (02) :1001-1008
[8]  
OKU K, 1994, IEE JAPAN T B, V114, P234
[9]  
OKU K, 1995, IEE JAPAN T B, V115, P1023
[10]   A NEW APPROACH TO HARMONIC COMPENSATION IN POWER-SYSTEMS - A COMBINED SYSTEM OF SHUNT PASSIVE AND SERIES ACTIVE-FILTERS [J].
PENG, FZ ;
AKAGI, H ;
NABAE, A .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1990, 26 (06) :983-990