Considerations of a shunt active filter based on voltage detection for installation on a long distribution feeder

被引:124
作者
Wada, K [1 ]
Fujita, H
Akagi, H
机构
[1] Tokyo Metropolitan Univ, Dept Elect Engn, Tokyo 1920397, Japan
[2] Tokyo Inst Technol, Dept Elect & Elect Engn, Tokyo 1528522, Japan
关键词
distributed-parameter representation; harmonic damping; harmonic propagation; power distribution systems; shunt active filters;
D O I
10.1109/TIA.2002.800584
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper deals with a curious phenomenon referred to as the "whack-a-mole" that may occur in a long-distance distribution feeder having many capacitors for power-factor correction. The idea of whack-a-mole is that installation of an active or passive filter on the feeder makes voltage harmonics increase on some buses, whereas it makes voltage harmonics decrease on other buses, especially at the point of installation. The distributed-parameter representation is applied to a simplified feeder, thus making it possible to perform analysis of the whack-a-mole. As a result, this analysis yields such a basic Way as to avoid the whack-a-mole. Moreover, both theory and experiment clarify that installation of the active filter acting as a harmonic terminator on the end bus of the feeder can damp out harmonic propagation throughout the feeder without causing any whack-a-mole.
引用
收藏
页码:1123 / 1130
页数:8
相关论文
共 9 条
[1]   New trends in active filters for power conditioning [J].
Akagi, H .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1996, 32 (06) :1312-1322
[2]   Control strategy and site selection of a shunt active filter for damping of harmonic propagation in power distribution systems [J].
Akagi, H .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) :354-363
[3]   A shunt active filter based on voltage detection for harmonic termination of a radial power distribution line [J].
Akagi, H ;
Fujita, H ;
Wada, K .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1999, 35 (03) :638-645
[4]   Harmonic measurements, analysis, and power factor correction in a modern steel manufacturing facility [J].
Andrews, D ;
Bishop, MT ;
Witte, JF .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1996, 32 (03) :617-624
[5]   HARMONIC RESONANCE AT A MEDIUM-SIZED INDUSTRIAL-PLANT [J].
CURRENCE, EJ ;
PLIZGA, JE ;
NELSON, HN .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1995, 31 (04) :682-690
[6]  
Oku K., 1994, Transactions of the Institute of Electrical Engineers of Japan, Part B, V114-B, P234
[7]  
Oku K., 1995, Transactions of the Institute of Electrical Engineers of Japan, Part B, V115-B, P1023
[8]  
SUMIYA H, 1995, DENKI GENBA GIJYUTU, V34, P23
[9]  
TERMAN FE, 1963, ANAL TRANSMISSION FI, P354