Study on AC flashover performance and discharge process of polluted and iced IEC standard suspension insulator string

被引:74
作者
Jiang, Xingliang [1 ]
Wang, Shaohua [1 ]
Zhang, Zhijin [1 ]
Xie, Shujiao [1 ]
Wang, Yan [1 ]
机构
[1] Chongqing Univ, Dept Elect Engn, Chongqing 40044, Peoples R China
基金
中国国家自然科学基金;
关键词
AC flashover performance; discharge process; iced insulator string; icing; icing stress product;
D O I
10.1109/TPWRD.2006.876705
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
Based on the results of experimental investigations performed on the polluted and iced EEC standard suspension insulator strings of 3 similar to 21 units, the ac flashover performance and discharge process are discussed in this paper. It is put forward that the icing stress product (ISP), defined as the product of the ice-layer conductivity and the ice layer weight per centimeter of dry arc distance can be taken as a characteristic parameter to indicate the effect of ice accretions and contaminants on the flashover voltage. The flashover stress of an ice-covered insulator string can be expressed as a power function of ISP and has a linear relationship with the length of the insulator string. The partial arc of an iced insulator string is initiated by the breakdown of the air gaps between the tips of icicles and iced insulator surface and the persistence is much longer than that of a polluted insulator string.
引用
收藏
页码:472 / 480
页数:9
相关论文
共 31 条
[1]
[Anonymous], 1995, 4 IEEE
[2]
[Anonymous], 2002, ICE ACCRETION TRANSM
[3]
FLASHOVER TESTS OF ARTIFICIALLY ICED INSULATORS [J].
CHARNESKI, MD ;
GAIBROIS, GL ;
WHITNEY, BF .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (08) :2429-2433
[4]
The cold-fog test [J].
Chisholm, WA ;
Ringler, KG ;
Erven, CC ;
Green, MA ;
Melo, O ;
Tam, Y ;
Nigol, O ;
Kuffel, J ;
Boyer, A ;
Pavasars, IK ;
Macedo, FX ;
Sabiston, JK ;
Caputo, RB .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (04) :1874-1880
[5]
CHISHOLM WA, 2000, P 2 INT WORKSH HIGH
[6]
CHISHOLM WA, 1998, TR110296 EPRI
[7]
Flashover performance of ice-covered insulators [J].
Farzaneh, M ;
Kiernicki, J .
CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING-REVUE CANADIENNE DE GENIE ELECTRIQUE ET INFORMATIQUE, 1997, 22 (03) :95-109
[8]
AC FLASHOVER PERFORMANCE OF INSULATORS COVERED WITH ARTIFICIAL ICE [J].
FARZANEH, M ;
DRAPEAU, JF .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (02) :1038-1051
[9]
Insulator icing test methods and procedures a position paper prepared by the IEEE task force on insulator icing test methods [J].
Farzaneh, M ;
Baker, T ;
Bernstorf, A ;
Brown, K ;
Chisholm, WA ;
de Tourreil, C ;
Drapeau, JF ;
Fikke, S ;
George, JM ;
Gnandt, E ;
Grisham, T ;
Gutman, I ;
Hartings, R ;
Kremer, R ;
Powell, G ;
Rolfseng, L ;
Rozek, T ;
Ruff, DL ;
Shaffner, D ;
Sklenicka, V ;
Sundararajan, R ;
Yu, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (04) :1503-1515
[10]
Selection of station insulators with respect to ice and snow - Part I: Technical context and environmental exposure [J].
Farzaneh, M ;
Baker, T ;
Bernstorf, A ;
Burnham, JT ;
Carreira, T ;
Cherney, E ;
Chisholm, WA ;
Christman, R ;
Cole, R ;
Cortinas, J ;
de Tourreil, C ;
Drapeau, JF ;
Farzaneh-Dehkordi, J ;
Fikke, S ;
Gorur, R ;
Grisham, T ;
Gutman, I ;
Kuffel, J ;
Phillips, A ;
Powell, G ;
Rolfseng, L ;
Roy, M ;
Rozek, T ;
Ruff, DL ;
Schwalm, A ;
Sklenicka, V ;
Stewart, G ;
Sundararajan, R ;
Szeto, M ;
Tay, R ;
Zhang, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) :264-270