Thermal overload tests on a 400-MVA power transformer with a special 2.5-p.u. short tune loading capability

被引:28
作者
Nordman, H [1 ]
Lahtinen, M
机构
[1] ABB Transmit Oy, FIN-65101 Vaasa, Finland
[2] Fingrid Oyj, Helsinki 00101, Finland
关键词
Eddy losses; leakage flux; overloading; power transformer; winding hot-spot;
D O I
10.1109/TPWRD.2002.807747
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Comprehensive load/thermal testing was performed on a 400/400/125-MVA transformer representing a new design generation for large power transformers with a short time emergency loadability of 2.5 p.u. This particular overloadability factor required special design features to control the very high leakage flux resulting from such a loading condition and hence ensure that the transformer satisfies existing standards limits on hot-spot. This paper presents these design features along with a description of a full-size transformer which was built for the sake of developing these flux control measures. Hot-spot temperature measurements in the windings and in the outer core packets and, structural parts under a number of overloading conditions are presented and discussed. The results confirm the soundness of the design to handle the 2.5-p.u. overloadability while satisfying the hot-spot requirement according to the existing loading guides for 1.5-p.u. overloading. The measurements also show that the hot-spots will rise much faster than what an exponential function based on the time constant of top oil would predict.
引用
收藏
页码:107 / 112
页数:6
相关论文
共 6 条
[1]  
*IEC, 1991, 354 IEC
[2]  
*IEEE, 1991, IEEE GUID LOAD MIN C, V57
[3]  
LAMPE W, 1984, 1202 CIGRE
[4]   AN INVESTIGATION OF THE THERMAL PERFORMANCE OF AN OIL FILLED TRANSFORMER WINDING [J].
PIERCE, LW ;
MCNUTT, WJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (03) :1347-1358
[5]  
Schad H., 1989, Bulletin des Schweizerischen Elektrotechnischen Vereins & des Verbandes Schweizerischer Elektrizitaetswerke, V80, P377
[6]  
1990, ELECTRA, V129