PCA-SVM-Based Automated Fault Detection and Diagnosis (AFDD) for Vapor-Compression Refrigeration Systems

被引:125
作者
Han, Hua [1 ]
Cao, Zhikun [1 ]
Gu, Bo [1 ]
Ren, Neng [2 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200030, Peoples R China
[2] York Wuxi Air Conditioning & Refrigerat Co Ltd, Wuxi, Peoples R China
来源
HVAC&R RESEARCH | 2010年 / 16卷 / 03期
基金
中国国家自然科学基金;
关键词
QUANTITATIVE MODEL; BUILDING SYSTEMS; OUTDOOR AIR; AHU; PERFORMANCE; PROGNOSTICS; STRATEGY; SENSORS; NUMBER; ARX;
D O I
10.1080/10789669.2010.10390906
中图分类号
O414.1 [热力学];
学科分类号
070201 [理论物理];
摘要
To improve the classification accuracy and reduce the training and classifting time, a novel automated fault detection and diagnosis (AFDD) strategy is proposed for vapor-compression refrigeration systems, which combines principle cotnponent analysis (PCA) feature extraction technology and the "one to others" (binary-decision-tree-based) multiclass support vector machine (SVM) classification algorithm. Eight typical faults were artificially introduced into a refrigeration system in the laboratory, and tests for normal and faulty conditions were carried out over a -5 degrees C-15 degrees C (23 degrees F similar to 59 degrees F) evaporating temperature and a 25 degrees C-60 degrees C (77 degrees F similar to 140 degrees F) condensing temperature. The data obtained for 16 variables are first preprocessed by PCA to get four comprehensive features (principle components) that account for over 85% of the cumulative percent value (CPV); the new sample data are then randomly split into training (70%) and testing (30%) sets as the input of an eight-layer SVM classifier for A POD. Results show that the proposed PCA-SVM strategy has better detection and diagnosis capability with more satisfying FDD accuracy and is less time consuming compared to other approaches, such as SVM without PCA, back propagation neural network (BPNN) and the "one to one" and "one to rest" multi-class SVM algorithms. In this sense, this study provides a promising AFDD strategy for vapor-compression refrigeration system application.
引用
收藏
页码:295 / 313
页数:19
相关论文
共 55 条
[11]
DEXTER A, 2001, INT ENERGY AGENCY BU
[12]
Fault detection and diagnosis based on improved PCA with JAA method in VAV systems [J].
Du, Zhimin ;
Jin, Xinqiao ;
Wu, Lizhou .
BUILDING AND ENVIRONMENT, 2007, 42 (09) :3221-3232
[13]
PCA-FDA-based fault diagnosis for sensors in VAV systems [J].
Du, Zhimin ;
Jin, Xinqiao ;
Wu, Lizhou .
HVAC&R RESEARCH, 2007, 13 (02) :349-367
[14]
A robot fault diagnostic tool for flow rate sensors in air dampers and VAV terminals [J].
Du, Zhimin ;
Jin, Xinqiao ;
Yang, Xuebin .
ENERGY AND BUILDINGS, 2009, 41 (03) :279-286
[15]
Joint diagnosis of process and sensor faults using principal component analysis [J].
Dunia, R ;
Qin, SJ .
CONTROL ENGINEERING PRACTICE, 1998, 6 (04) :457-469
[16]
Edward J.J., 1991, User's Guide to Principal Components
[18]
PREDICTIVE AND DIAGNOSTIC ASPECTS OF A UNIVERSAL THERMODYNAMIC MODEL FOR CHILLERS [J].
GORDON, JM ;
NG, KC .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1995, 38 (05) :807-818
[19]
A comparison of methods for multiclass support vector machines [J].
Hsu, CW ;
Lin, CJ .
IEEE TRANSACTIONS ON NEURAL NETWORKS, 2002, 13 (02) :415-425
[20]
ISAAC M, 2009, COMPUTER AIDED CHEM, V26, P267