Multimachine eigenvalue sensitivities of power system parameters

被引:61
作者
Wang, KW [1 ]
Chung, CY [1 ]
Tse, CT [1 ]
Tsang, KM [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Elect Engn, Hong Kong, Hong Kong, Peoples R China
关键词
dynamic stability; eigenvalue sensitivity; system parameter;
D O I
10.1109/59.867168
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Many publications have discussed the design/tuning of controller (e.g. PSS) to increase system damping, but the effect of general system parameter appears to be ignored, This paper enables these effects to be accurately assessed by the first and second order eigenvalue sensitivities with respect to any arbitrary system operating parameter (e.g. nodal injection, PV-voltage) or power network parameter (line impedance or transforme tap etc). Based on a highly versatile multimachine modeling technique that any practical system components (such as generators, SVC, series compensator etc) can be incorporated, the system matrix A can be expressed as a function of each system parameter of a multimachine system. The sensitivity approach is applied on an 8-machine system to discuss the system parameter effects and to take account of the range of operating condition in terms of multi-load levels by probabilistic approach.
引用
收藏
页码:741 / 747
页数:7
相关论文
共 12 条
[11]  
WANG KW, 1997, P APSCOM 97 HONG KON, P445
[12]  
WANG KW, INT C POW SYST TECHN, P829