Modeling, analysis, and implementation of parallel multi-inverter systems with instantaneous average-current-sharing scheme

被引:203
作者
Sun, X [1 ]
Lee, YS
Xu, DH
机构
[1] Hong Kong Polytech Univ, Dept Elect & Informat Engn, Kowloon, Hong Kong, Peoples R China
[2] Zhejiang Univ, Dept Elect Engn, Hangzhou 310027, Peoples R China
关键词
load sharing; multi-inverter system; parallel operation;
D O I
10.1109/TPEL.2003.810867
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Parallel multi-inverter systems can be designed to have the advantages of expandable output power, improved reliability, and easy N + X redundancy operation. However, a current-sharing control scheme has to be employed to enable the inverters to share the load current equally. A multi-inverter system with instantaneous average-current-sharing scheme is presented in this paper. By introducing a disturbance source to represent all the sources that may cause current unbalances, a model of the system can be built. Some key issues are discussed based on the model, including stability of the current-sharing controller, impedance characteristics and voltage regulation. Three experimental 110 Vac/1.1 KVA inverters are built and paralleled to verify the theoretical predictions.
引用
收藏
页码:844 / 856
页数:13
相关论文
共 32 条