A self-synchronizing instrument for harmonic source detection in power systems

被引:44
作者
Aiello, M [1 ]
Cataliotti, A [1 ]
Cosentino, V [1 ]
Nuccio, S [1 ]
机构
[1] Univ Palermo, Dept Elect Engn, I-90128 Palermo, Italy
关键词
harmonic analysis; harmonic distortion; phase-locked loops (PLLs); power measurement; power quality; power system harmonics; power system measurements;
D O I
10.1109/TIM.2004.834600
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The deregulation of energy markets holds out new prospects for contracts between customers and utilities, in which the price of energy can depend on voltage quality and load characteristics, as well as on the responsibility for disturbances caused to supply voltage in power systems. In this context, harmonic source detection is one of the main problems because of equipment sensibility and the proliferation of loads which absorb nonsinusoidal currents. In this paper, the authors present a new instrument based on a time-domain,method for the detection of harmonic active powers in three-phase systems, which can be usefully applied even in the presence of unbalance or asymmetry. The amplitude and sign of harmonic powers can be measured directly, and no spectral analysis is required for the evaluation of the amplitudes and phase angles of supply currents. Moreover, the instrument is able to synchronize itself with the input signal to measure the total distortion factors of voltages and currents, supply voltage unbalance, and harmonic voltage amplitudes. Theoretical aspects are discussed, the measurement accuracy is evaluated, and the experimental results are presented. Finally, a comparison is made with a commercial instrument.
引用
收藏
页码:15 / 23
页数:9
相关论文
共 25 条
[11]   Evaluation of single-point measurements method for harmonic pollution cost allocation [J].
Davis, EJ ;
Emanuel, AE ;
Pileggi, DJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (01) :14-18
[12]  
*EC, 610003 IEC
[13]   ON THE ASSESSMENT OF HARMONIC POLLUTION [J].
EMANUEL, AE .
IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (03) :1693-1698
[14]   A NEW APPROACH TO THE DEFINITION OF POWER COMPONENTS IN 3-PHASE SYSTEMS UNDER NONSINUSOIDAL CONDITIONS [J].
FERRERO, A ;
SUPERTIFURGA, G .
IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 1991, 40 (03) :568-577
[15]  
Gardner F., 1966, PHASELOCK TECHNIQUES
[16]  
*IEEE, 2000, 14592000 IEEE
[17]   Operation of a phase locked loop system under distorted utility conditions [J].
Kaura, V ;
Blasko, V .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (01) :58-63
[18]  
Oppenheim AV, 1975, DIGITAL SIGNAL PROCE
[19]   An evaluation of some alternative methods of power resolution in a large industrial plant [J].
Pretorius, JHC ;
van Wyk, JD ;
Swart, PH .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (03) :1052-1059
[20]   On techniques for the localisation of multiple distortion sources in three-phase networks: Time domain verification. [J].
Rens, APJ ;
Swart, PH .
EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2001, 11 (05) :317-322