Micro-combined cooling, heating and power systems hybrid electric-thermal load following operation

被引:135
作者
Mago, P. J. [1 ]
Chamra, L. M. [2 ]
Ramsay, J. [1 ]
机构
[1] Mississippi State Univ, Dept Mech Engn, Mississippi State, MS 39762 USA
[2] Oakland Univ, Sch Engn & Comp Sci, Rochester, MI 48309 USA
关键词
mCCHP systems; Hybrid operation strategy; Primary energy consumption; ENERGY; COST;
D O I
10.1016/j.applthermaleng.2009.12.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
Micro-combined cooling, heating and power (mCCHP), typically designated as less than 30 kW electric, is a technology that generates electricity at or near the place where it is used. The waste heat from the electricity generation can be used for space cooling, space heating, or water heating. The operation of mCCHP systems, while obviously dependent upon the seasonal atmospheric conditions, which determine the building thermal and power demand, is ultimately controlled by the operation strategy. Two of the most common operation strategies are to run the prime mover in accordance to either electrical or thermal demand. In this study, a mCCHP system operating following a hybrid electric-thermal load (FHL) is proposed and investigated. This operation strategy is evaluated and compared with mCCHP systems operating following the electric load (FEL) and operating following the thermal load (FTL). This evaluation and comparison is based on site energy consumption (SEC), primary energy consumption (PEC), operational cost, and carbon dioxide emission reduction (CDE). Results show that mCCHP systems operated following the hybrid electric-thermal load have better performance than mCCHP-FEL and mCCHP-FTL.. mCCHP-FHL showed higher reductions of PEC, operational cost, and carbon dioxide emissions than the ones obtained for the other two operation strategies for the evaluated case. (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:800 / 806
页数:7
相关论文
共 14 条
[1]   A new approach to exergoeconomic analysis and design of variable demand energy systems [J].
Cardona, E ;
Piacentino, A .
ENERGY, 2006, 31 (04) :490-515
[2]   A methodology for sizing a trigeneration plant in mediterranean areas [J].
Cardona, E ;
Piacentino, A .
APPLIED THERMAL ENGINEERING, 2003, 23 (13) :1665-1680
[3]   Assessment of the greenhouse gas emissions from cogeneration and trigeneration systems. Part I: Models and indicators [J].
Chicco, Gianfranco ;
Mancarella, Pierluigi .
ENERGY, 2008, 33 (03) :410-417
[4]  
*EN SIM SOFTW, ENERGYPLUS
[5]   Analysis of cooling, heating, and power systems based on site energy consumption [J].
Furno, Nelson ;
Mago, Pedro J. ;
Chamra, Louay M. .
APPLIED ENERGY, 2009, 86 (06) :928-932
[6]  
Jalalzadeh-Azar A.A., 2004, ASHRAE T, P85
[7]   Methodology to perform a non-conventional evaluation of cooling, heating, and power systems [J].
Mago, P. J. ;
Fumo, N. ;
Chamra, L. M. .
PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART A-JOURNAL OF POWER AND ENERGY, 2007, 221 (A8) :1075-1087
[8]   Performance analysis of CCHP and CHP systems operating following the thermal and electric load [J].
Mago, P. J. ;
Fumo, N. ;
Chamra, L. M. .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2009, 33 (09) :852-864
[9]   Assessment of the greenhouse gas emissions from cogeneration and trigeneration systems. Part II: Analysis techniques and application cases [J].
Mancarella, Pierluigi ;
Chicco, Gianfranco .
ENERGY, 2008, 33 (03) :418-430
[10]   Potential market niches for biomass energy with CO2 capture and storage -: Opportunities for energy supply with negative CO2 emissions [J].
Möllersten, K ;
Yan, JY ;
Moreira, JR .
BIOMASS & BIOENERGY, 2003, 25 (03) :273-285