Feature extraction of partial discharge signals using the wavelet packet transform and classification with a probabilistic neural network

被引:120
作者
Evagorou, D. [1 ]
Kyprianou, A. [2 ]
Lewin, P. L. [3 ]
Stavrou, A. [4 ]
Efthymiou, V. [4 ]
Metaxas, A. C. [5 ]
Georghiou, G. E. [1 ]
机构
[1] Univ Cyprus, Dept Elect & Comp Engn, CY-1678 Nicosia, Cyprus
[2] Univ Cyprus, Dept Mech & Mfg Engn, CY-1678 Nicosia, Cyprus
[3] Univ Southampton, Sch Elect & Comp Sci, Tony Davies High Voltage Lab, Southampton SO17 1BJ, Hants, England
[4] Elect Author Cyprus, Nicosia, Cyprus
[5] Univ Cambridge, Dept Engn, Elect Utilisat Grp, Cambridge CB2 1TN, England
关键词
PD PULSE SHAPES; RECOGNITION;
D O I
10.1049/iet-smt.2009.0023
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Partial discharge (PD) classification in power cable accessories and high voltage equipment in general is essential in evaluating the severity of the damage in the insulation. In this article, the PD classification was realised as a two-fold process. Firstly, measurements taken from a high-frequency current transformer (HFCT) sensor were represented as features by means of a transformation to the classifier and secondly, the probabilistic neural network (PNN) classifier itself was capable of effectively recognising features coming from different types of discharges. The feature that was used as a fingerprint for PD characterisation was extracted from the moments of the probability density function (PDF) of the wavelet coefficients at various scales, obtained through the wavelet packets transformation. The PNN classifier was used to classify the PDs and assess the suitability of this feature vector in PD classification. Four types of artificial PDs were created in a high voltage laboratory, namely corona discharge in air, floating discharge in oil, internal discharge in oil and surface discharge in air, at different applied voltages, and were used to train the PNN algorithm. The results obtained here (97.49, 91.9, 100 and 99.8% for the corona, the floating, the internal and the surface discharges, respectively) are very encouraging for the use of PNN in PD classification with this particular feature vector. This article suggests a feature extraction and classification algorithm for PD classification, which when combined together reduced the dimensionality of the feature space to a manageable dimension, and achieved very high levels of classification.
引用
收藏
页码:177 / 192
页数:16
相关论文
共 56 条
[41]  
PRESS SJ, 1982, APPL MULTIVARIATE AN, pCH13
[42]   Trends in partial discharge pattern classification: A survey [J].
Sahoo, NC ;
Salama, MMA ;
Bartnikas, R .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2005, 12 (02) :248-264
[43]   Fuzzy logic applied to PD pattern classification [J].
Salama, MMA ;
Bartnikas, R .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2000, 7 (01) :118-123
[44]   Determination of neural-network topology for partial discharge pulse pattern recognition [J].
Salama, MMA ;
Bartnikas, R .
IEEE TRANSACTIONS ON NEURAL NETWORKS, 2002, 13 (02) :446-456
[45]  
Scholkopf B., 2001, Learning with Kernels: Support Vector Machines, Regularization, Optimization, and Beyond
[46]   SVM classification of contaminating particles in liquid dielectrics using higher order statistics of electrical and acoustic PD measurements [J].
Sharkawy, R. M. ;
Mangoubi, R. S. ;
Abdel-Galil, T. K. ;
Salama, M. M. A. ;
Bartnikas, R. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2007, 14 (03) :669-678
[47]   GENERATION OF POLYNOMIAL DISCRIMINANT FUNCTIONS FOR PATTERN RECOGNITION [J].
SPECHT, DF .
IEEE TRANSACTIONS ON ELECTRONIC COMPUTERS, 1967, EC16 (03) :308-&
[48]   MAXIMUM-LIKELIHOOD TRAINING OF PROBABILISTIC NEURAL NETWORKS [J].
STREIT, RL ;
LUGINBUHL, TE .
IEEE TRANSACTIONS ON NEURAL NETWORKS, 1994, 5 (05) :764-783
[49]   Comparison of on-line partial discharge detection methods for HV cable joints [J].
Tian, Y ;
Lewin, PL ;
Davies, AE ;
Swingler, SG ;
Sutton, SJ ;
Hathaway, GM .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2002, 9 (04) :604-615
[50]  
Tian Y, 2000, IEE CONF PUBL, P503, DOI 10.1049/cp:20000560