PERFORMANCE EVALUATION FOR A THERMAL SWING HONEYCOMB ROTOR ADSORBER USING A HUMIDITY CHART

被引:36
作者
KODAMA, A
GOTO, M
HIROSE, T
KUMA, T
机构
[1] KUMAMOTO UNIV,GRAD SCH SCI & TECHNOL,DEPT IND SCI,KUMAMOTO 860,JAPAN
[2] SEIBU GIKEN CO LTD,SASAGURI,FUKUOKA 81124,JAPAN
关键词
ADSORPTION; THERMAL SWING OPERATION; HONEYCOMB ADSORBER; SILICA GEL; DEHUMIDIFICATION; HUMIDITY CHART;
D O I
10.1252/jcej.28.19
中图分类号
TQ [化学工业];
学科分类号
0817 ;
摘要
Adsorption/desorption behavior and simultaneous heat and mass transfer in a honeycomb adsorber were investigated using a humidity chart, It was found that the dehumidifying performance is sometimes decreased remarkably owing to the mass/heat balance limitation when the feed humidity is high or regeneration temperature is low. A prediction method is proposed for the design principle of honeycomb adsorbers by taking into account the optimal rotation speed and the regeneration air velocity obtained from the graphical solution using a humidity chart, The method is simple to use, without complicated computation and it is useful to avoid the serious influence of by the mass/heat balance limitation, At a process air velocity of 1m/s, by considering the relation between the optimal rotation speed and the moderate regeneration air velocity obtained using a graphical method, the product air humidity decreases to a value near to the thermodynamic limit.
引用
收藏
页码:19 / 24
页数:6
相关论文
共 14 条
[1]   PREDICTION OF HEAT AND MASS REGENERATOR PERFORMANCE USING NONLINEAR ANALOGY METHOD .1. BASIS [J].
BANKS, PJ .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1985, 107 (01) :222-229
[2]  
BANKS PJ, 1985, J HEAT TRANSFER, V107, P229
[3]   COMBINED HEAT AND MASS-TRANSFER IN REGENERATORS WITH HYGROSCOPIC MATERIALS [J].
HOLMBERG, RB .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1979, 101 (02) :205-210
[4]   HEAT AND MASS-TRANSFER IN ROTARY HEAT-EXCHANGERS WITH NON-HYGROSCOPIC ROTOR MATERIALS [J].
HOLMBERG, RB .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1977, 99 (02) :196-202
[5]  
JURINAK JJ, 1984, J HEAT TRANS-T ASME, V106, P638, DOI 10.1115/1.3246728
[6]   STATISTICAL-ANALYSIS OF A SILICA-GEL ROTARY DEHUMIDIFIER [J].
KINI, A ;
WAUGMAN, DG ;
KETTLEBOROUGH, CF .
DRYING TECHNOLOGY, 1993, 11 (03) :635-647
[7]   EXPERIMENTAL-STUDY OF OPTIMAL OPERATION FOR A HONEYCOMB ADSORBER OPERATED WITH THERMAL SWING [J].
KODAMA, A ;
GOTO, M ;
HIROSE, T ;
KUMA, T .
JOURNAL OF CHEMICAL ENGINEERING OF JAPAN, 1993, 26 (05) :530-535
[8]   TEMPERATURE PROFILE AND OPTIMAL ROTATION SPEED OF A HONEYCOMB ROTOR ADSORBER OPERATED WITH THERMAL SWING [J].
KODAMA, A ;
GOTO, M ;
HIROSE, T ;
KUMA, T .
JOURNAL OF CHEMICAL ENGINEERING OF JAPAN, 1994, 27 (05) :644-649
[9]  
KUMA T, 1989, Patent No. 125614
[10]  
Kuma T., 1989, [No title captured], Patent No. [4,886,769, 4886769]