PHYSICAL, CHEMICAL AND MICROBIOLOGICAL WATER CHARACTERISTICS ASSOCIATED WITH THE OCCURRENCE OF LEGIONELLA IN COOLING-TOWER SYSTEMS

被引:34
作者
KUSNETSOV, JM
MARTIKAINEN, PJ
JOUSIMIESSOMER, HR
VAISANEN, ML
TULKKI, AI
AHONEN, HE
NEVALAINEN, AI
机构
[1] POSTS & TELECOMMUN FINLAND,SF-00101 HELSINKI,FINLAND
[2] KTL,DEPT BACTERIOL,SF-00300 HELSINKI,FINLAND
关键词
LEGIONELLA; BACTERIA; COOLING TOWER SYSTEM; WATER PHYSICS AND CHEMISTRY; OCCURRENCE;
D O I
10.1016/0043-1354(93)90198-Q
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The occurrence of Legionella in water of 30 cooling tower systems was studied, as well as the relationship of its occurrence with the physical, chemical and microbiological characteristics of the waters. The samples were concentrated by membrane filtration and one part of the concentrate was acid washed. Three types of culture media, MWY, CCVC and BCYEalpha were used. Fourteen (47%) of the cooling systems were Legionella-positive. Numbers of Legionella in the positive systems varied between 50 and 490,000 cfu/l. Legionella pneumophila was the dominant isolate, and the serogroups 6 and 1 were the commonest ones. There was no statistically significant difference in mean water temperature between the Legionella-positive (27-degrees-C) and -negative (24-degrees-C) systems. The total number of bacteria (AODC) was lower in the Legionella-positive than in the negative systems. Also the nutrient concentrations were generally lower in the Legionella-positive cooling systems. The results suggest that different factors regulate the occurrence of Legionella than that of overall bacterial populations in the cooling tower systems.
引用
收藏
页码:85 / 90
页数:6
相关论文
共 33 条
[1]   COMMUNITY-ACQUIRED LEGIONNAIRES-DISEASE ASSOCIATED WITH A COOLING-TOWER - EVIDENCE FOR LONGER-DISTANCE TRANSPORT OF LEGIONELLA-PNEUMOPHILA [J].
ADDISS, DG ;
DAVIS, JP ;
LAVENTURE, M ;
WAND, PJ ;
HUTCHINSON, MA ;
MCKINNEY, RM .
AMERICAN JOURNAL OF EPIDEMIOLOGY, 1989, 130 (03) :557-568
[2]  
[Anonymous], 1985, STANDARD METHODS EXA
[3]   ISOLATION OF PROTOZOA FROM WATER ASSOCIATED WITH A LEGIONELLOSIS OUTBREAK AND DEMONSTRATION OF INTRACELLULAR MULTIPLICATION OF LEGIONELLA-PNEUMOPHILA [J].
BARBAREE, JM ;
FIELDS, BS ;
FEELEY, JC ;
GORMAN, GW ;
MARTIN, WT .
APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 1986, 51 (02) :422-424
[4]   MAINTENANCE OF COOLING-TOWERS FOLLOWING 2 OUTBREAKS OF LEGIONNAIRES-DISEASE IN A CITY [J].
BHOPAL, RS ;
BARR, G .
EPIDEMIOLOGY AND INFECTION, 1990, 104 (01) :29-38
[5]   ISOLATION OF LEGIONELLA SPP FROM ENVIRONMENTAL WATER SAMPLES BY LOW-PH TREATMENT AND USE OF A SELECTIVE MEDIUM [J].
BOPP, CA ;
SUMNER, JW ;
MORRIS, GK ;
WELLS, JG .
JOURNAL OF CLINICAL MICROBIOLOGY, 1981, 13 (04) :714-719
[6]  
COLBOURNE JS, 1986, ISRAEL J MED SCI, V22, P633
[7]   OUTBREAK OF LEGIONNAIRES-DISEASE ASSOCIATED WITH A CONTAMINATED AIR-CONDITIONING COOLING-TOWER [J].
DONDERO, TJ ;
RENDTORFF, RC ;
MALLISON, GF ;
WEEKS, RM ;
LEVY, JS ;
WONG, EW ;
SCHAFFNER, W .
NEW ENGLAND JOURNAL OF MEDICINE, 1980, 302 (07) :365-370
[8]   IMPROVED SEMISELECTIVE MEDIUM FOR ISOLATION OF LEGIONELLA-PNEUMOPHILA FROM CONTAMINATED CLINICAL AND ENVIRONMENTAL SPECIMENS [J].
EDELSTEIN, PH .
JOURNAL OF CLINICAL MICROBIOLOGY, 1981, 14 (03) :298-303
[9]   COMPARATIVE-STUDY OF SELECTIVE MEDIA FOR ISOLATION OF LEGIONELLA-PNEUMOPHILA FROM POTABLE WATER [J].
EDELSTEIN, PH .
JOURNAL OF CLINICAL MICROBIOLOGY, 1982, 16 (04) :697-699
[10]  
EDELSTEIN PH, 1985, 691W111F2 VA MED CTR