NEW APPROACH TO DIRECTIONAL FAULT LOCATION FOR OVERHEAD POWER DISTRIBUTION FEEDERS

被引:15
作者
JOHNS, AT [1 ]
LAI, LL [1 ]
ELHAMI, M [1 ]
DARUVALA, DJ [1 ]
机构
[1] CITY UNIV LONDON,DEPT ELECT ELECTR & INFORMAT ENGN,LONDON EC1V 0HB,ENGLAND
关键词
FAULT LOCATION; DETECTION; OVERHEAD LINES;
D O I
10.1049/ip-c.1991.0044
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The results of investigations into a new approach to fault localisation in overhead distribution systems are presented. The method proposed does not use the fundamental power frequency currents but is based on detecting fault-induced high frequency components on distribution lines. This should enable the detection of discharges from the low-level breakdown of insulators, which cannot be detected by conventional methods. The fault direction is determined by filtering the output voltage from stack tuners and comparing the resulting signal levels on each side of a tuned trap circuit unit. Simulation results are used to illustrate the basic features of the performance of the new scheme on a simple radial 11 kV feeder system.
引用
收藏
页码:351 / 357
页数:7
相关论文
共 16 条
[1]   ULTRA HIGH-SPEED RELAY FOR EHV-UHV TRANSMISSION-LINES - DEVELOPMENT, DESIGN AND APPLICATION [J].
CHAMIA, M ;
LIBERMAN, S .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1978, 97 (06) :2104-2116
[2]  
CLARKE GJ, 1985, IEE PUB, V249, P199
[3]   POWER SYSTEM TRANSIENTS CAUSED BY ARCING FAULTS [J].
CORNICK, KJ ;
KO, YM ;
PEK, B .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1981, 128 (01) :18-27
[4]  
DOMMEL HW, 1978, JAN IEEE PES WINT M, P214
[5]  
Galloway RH, 1964, P I ELECTR ENG, V111, P2051
[6]   PERFORMANCE OF DISTANCE PROTECTION OF EHV FEEDERS UTILIZING SHUNT-REACTOR ARRANGEMENTS FOR ARC SUPPRESSION AND VOLTAGE CONTROL [J].
JOHNS, AT ;
ELNOUR, M ;
AGGARWAL, RK .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1980, 127 (05) :304-316
[7]   NEW APPROACH TO POWER-LINE PROTECTION BASED UPON THE DETECTION OF FAULT INDUCED HIGH-FREQUENCY SIGNALS [J].
JOHNS, AT ;
AGRAWAL, P .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1990, 137 (04) :307-313
[8]   DIGITAL-SIMULATION OF FAULTED EHV TRANSMISSION-LINES WITH PARTICULAR REFERENCE TO VERY-HIGH-SPEED PROTECTION [J].
JOHNS, AT ;
AGGARWAL, RK .
PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1976, 123 (04) :353-359
[9]   DIGITAL-SIMULATION OF EHV SYSTEMS UNDER SECONDARY ARCING CONDITIONS ASSOCIATED WITH SINGLE-POLE AUTORECLOSURE [J].
JOHNS, AT ;
ALRAWI, AM .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1982, 129 (02) :49-58
[10]  
LOGAN JT, 1937, ARC FREQUENCY COMPON