UTILIZATION OF INTERRUPTED ENERGY ASSESSMENT RATES IN GENERATION AND TRANSMISSION-SYSTEM PLANNING

被引:18
作者
BILLINTON, R
OTENGADJEI, J
机构
[1] Power System Research Group, Department of Electrical Engineering, University of Saskatchewan, Saskatoon, Saskatchewan
关键词
RELIABILITY COST WORTH ANALYSIS; INTERRUPTION COSTS; COMPOSITE GENERATION AND TRANSMISSION SYSTEMS;
D O I
10.1109/59.119273
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
One approach which can be used to determine the optimum level of electric reliability is to compare the marginal cost of providing reliability with the marginal worth of that reliability. The worth of an increment of reliability can be considered to be the change in the interruption costs associated with the change in reliability level. This paper briefly illustrates methods of using customer interruption cost data to obtain a factor which can be utilized to relate customer losses to the worth of electric service reliability in both generation and composite generation and transmission systems. This factor is designated as the Interrupted Energy Assessment Rate (IEAR). The paper also illustrates how the IEAR index can be utilized in a basic generation and transmission facilities reinforcement study.
引用
收藏
页码:1245 / 1253
页数:9
相关论文
共 16 条
  • [1] COMPARISON OF 2 ALTERNATE METHODS TO ESTABLISH AN INTERRUPTED ENERGY ASSESSMENT RATE
    BILLINTON, R
    OTENGADJEI, J
    GHAJAR, R
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 1987, 2 (03) : 751 - 757
  • [2] BILLINTON R, 1987, RELIABILITY ASSESSME
  • [3] Billinton R., 1984, RELIABILITY EVALUATI
  • [4] BILLINTON R, 1989, IEEE89 SM6453 PWRS
  • [5] BILLINTON R, 1984, IEE ELECTRONICS MAR, P231
  • [6] BILLINTON R, 1989, IEEE89 WM0357 PWRS
  • [7] KUMAR S, 1986, 86SP141 CAN EL ASS 3, V25
  • [8] MEDICHERLA TKP, 1980, IEE P C, V127, P72
  • [9] OTENGADJEI J, 1989, IEEE89 SM7170 PWRS P
  • [10] OTENGADJEI J, 1988, IEE P C, V135