ISOLATION OF AMEBAS AND PSEUDOMONAS AND LEGIONELLA SPP FROM EYEWASH STATIONS

被引:66
作者
PASZKOKOLVA, C
YAMAMOTO, H
SHAHAMAT, M
SAWYER, TK
MORRIS, G
COLWELL, RR
机构
[1] UNIV MARYLAND,DEPT MICROBIOL,COLLEGE PK,MD 20742
[2] UNIV MARYLAND,DEPT ENVIRONM SAFETY,COLLEGE PK,MD 20742
[3] RESCON ASSOCIATES INC,ROYAL OAK,MD 21662
关键词
D O I
10.1128/AEM.57.1.163-167.1991
中图分类号
Q81 [生物工程学(生物技术)]; Q93 [微生物学];
学科分类号
071005 ; 0836 ; 090102 ; 100705 ;
摘要
Forty eyewash units were sampled for protozoa, bacteria, and fungi. Total heterotrophic bacterial counts on nutrient agar and R2A agar (Difco Laboratories, Detroit, Mich.) ranged from 0 to 10(5) CFU/ml, with Pseudomonas spp. being the most frequently isolated. Total counts of 10(4) and 10(8) cells per ml were obtained with the acridine orange staining procedure. All samples were examined for Legionella spp. by direct fluorescent-antibody staining and by culturing on buffered charcoal-yeast extract agar containing-alpha-ketoglutarate and glycine and supplemented with cycloheximide, vancomycin, and polymyxin B. DNA-DNA hybridization was used to confirm identification of the Legionella isolates. Legionellae were detected in 35 of 40 (87.5%) samples by direct fluorescent-antibody staining, with 3 samples yielding both Legionella spp. and amoebae. Amoebae identified as Hartmannella, Vahlkampfia, Acanthamoeba, and Cochliopodium spp. were detected in 19 of 40 (47.5%) samples. Sabouraud dextrose agar was used to obtain a crude estimate of viable fungal populations. pH, hardness, and ammonia, alkalinity, chlorine, copper, and iron contents were recorded for all water samples collected from eyewash stations; 33% of the samples had greater-than-or-equal-to 10 mg of CO2 per liter. It is concluded that eyewash stations not regularly flushed and/or cleaned and used to flush traumatized eye tissue may be a source of infection and can contaminate laboratory environments via aerosol transmission.
引用
收藏
页码:163 / 167
页数:5
相关论文
共 24 条
[1]   ISOLATION OF LEGIONELLA SPP FROM ENVIRONMENTAL WATER SAMPLES BY LOW-PH TREATMENT AND USE OF A SELECTIVE MEDIUM [J].
BOPP, CA ;
SUMNER, JW ;
MORRIS, GK ;
WELLS, JG .
JOURNAL OF CLINICAL MICROBIOLOGY, 1981, 13 (04) :714-719
[2]  
BOTZENHART K, 1986, ZBL HYG UMWELTMED, V183, P79
[3]   RAPID PROCEDURE TO DETERMINE THE DNA-BASE COMPOSITION FROM SMALL AMOUNTS OF GRAM-POSITIVE BACTERIA [J].
EZAKI, T ;
SAIDI, SM ;
LIU, SL ;
HASHIMOTO, Y ;
YAMAMOTO, H ;
YABUUCHI, E .
FEMS MICROBIOLOGY LETTERS, 1990, 67 (1-2) :127-130
[4]  
EZAKI T, 1990, EUR J CLIN MICROBIOL, V9, P214
[5]  
FENSTERSHEIB MD, 1990, LANCET, P35
[6]   INTRACELLULAR MULTIPLICATION OF LEGIONELLA-PNEUMOPHILA IN AMEBAS ISOLATED FROM HOSPITAL HOT WATER TANKS [J].
FIELDS, BS ;
SANDEN, GN ;
BARBAREE, JM ;
MORRILL, WE ;
WADOWSKY, RM ;
WHITE, EH ;
FEELEY, JC .
CURRENT MICROBIOLOGY, 1989, 18 (02) :131-137
[7]   1ST ISOLATION OF LEGIONELLA-GORMANII FROM HUMAN-DISEASE [J].
GRIFFITH, ME ;
LINDQUIST, DS ;
BENSON, RF ;
THACKER, WL ;
BRENNER, DJ ;
WILKINSON, HW .
JOURNAL OF CLINICAL MICROBIOLOGY, 1988, 26 (02) :380-381
[8]  
HAMBURG A, 1980, OPHTHALMOLOGICA, V181, P75
[9]  
HILTON E, 1983, LANCET, V1, P1318
[10]   USE OF NUCLEPORE FILTERS FOR COUNTING BACTERIA BY FLUORESCENCE MICROSCOPY [J].
HOBBIE, JE ;
DALEY, RJ ;
JASPER, S .
APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 1977, 33 (05) :1225-1228