Performance prediction of an air-cooled steam condenser using UDF method

被引:47
作者
He, W. F. [1 ]
Dai, Y. P. [1 ]
Wang, J. F. [1 ]
Li, M. Q. [1 ]
Ma, Q. Z. [2 ]
机构
[1] Xi An Jiao Tong Univ, Turbomachinery Res Inst, Xian 710049, Shaanxi, Peoples R China
[2] Shanxi Elect Power Res Inst, Taiyuan 030001, Shanxi, Peoples R China
关键词
Air-cooled steam condenser; Wind condition; User defined function; Heat transfer rate; Back pressure; THERMAL POWER-PLANT; HEAT-EXCHANGERS; FAN PERFORMANCE; FLOW LOSSES; SIMULATION; RECIRCULATION; SYSTEM;
D O I
10.1016/j.applthermaleng.2012.06.020
中图分类号
O414.1 [热力学];
学科分类号
摘要
The performance of air-cooled steam condensers (ACSCs) is always influenced under the unfavorable effect of wind conditions. It is significant to understand the mechanism of such influences so as to improve and optimize the performance of the condensers. In this study, the flow field around a 2 x 600 MW direct air-cooled power plant at different wind speeds and ambient temperatures is numerically simulated, and the relevant influence mechanism is illustrated. User defined function (UDF) based on steam properties, which plays a critical role in the prediction of condenser back pressures, is proposed to simulate the condensation of the turbine exhaust in the exchangers. It is found that wind speed has great influences on the performance of air-cooled steam condensers due to the variation of pressure distribution around the ACSC platform. Heat transfer rate degrades rapidly, while the fan flow rate rises slightly, with the increase of ambient temperature because the heat transfer potential between ambient air and the turbine exhaust is determined by their temperature difference. Finally, the stable back pressures corresponding to each prescribed wind condition are forecasted according to the comparison between the computational heat transfer rate and the ideal heat rejection. (C) 2012 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1339 / 1350
页数:12
相关论文
共 11 条
[1]   Numerical investigation of fan performance in a forced draft air-cooled steam condenser [J].
Bredell, JR ;
Kröger, DG ;
Thiart, GD .
APPLIED THERMAL ENGINEERING, 2006, 26 (8-9) :846-852
[2]   Numerical simulation of heat transfer performance of an air-cooled steam condenser in a thermal power plant [J].
Gao, Xiufeng ;
Zhang, Chengwei ;
Wei, Jinjia ;
Yu, Bo .
HEAT AND MASS TRANSFER, 2009, 45 (11) :1423-1433
[3]   Wind tunnel simulation of exhaust recirculation in an air-cooling system at a large power plant [J].
Gu, Zhifu ;
Chen, Xuerei ;
Lubitz, William ;
Li, Yan ;
Luo, Wonlin .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2007, 46 (03) :308-317
[4]   Numerical investigation of hot air recirculation of air-cooled condensers at a large power plant [J].
Liu, Peiqing ;
Duan, Huishen ;
Zhao, Wanli .
APPLIED THERMAL ENGINEERING, 2009, 29 (10) :1927-1934
[5]   Plenum chamber flow losses in forced draught air-cooled heat exchangers [J].
Meyer, CJ ;
Kroger, DG .
APPLIED THERMAL ENGINEERING, 1998, 18 (9-10) :875-893
[6]   Air-cooled heat exchanger inlet flow losses [J].
Meyer, CJ ;
Kröger, DG .
APPLIED THERMAL ENGINEERING, 2001, 21 (07) :771-786
[7]   EFFECT OF INLET FLOW DISTORTIONS ON FAN PERFORMANCE IN FORCED DRAFT AIR-COOLED HEAT-EXCHANGERS [J].
SALTA, CA ;
KROGER, DG .
HEAT RECOVERY SYSTEMS & CHP, 1995, 15 (06) :555-561
[8]   Effect of cross-flow on the performance of air-cooled heat exchanger fans [J].
Stinnes, WH ;
von Backström, TW .
APPLIED THERMAL ENGINEERING, 2002, 22 (12) :1403-1415
[9]  
Tao W.Q., 2002, Numerical heat transfer (in Chinese), V2nd
[10]   NUMERICAL-SIMULATION OF THE FLOW-FIELD NEAR AN AXIAL-FLOW FAN OPERATING UNDER DISTORTED INFLOW CONDITIONS [J].
THIART, GD ;
VONBACKSTROM, TW .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 1993, 45 (02) :189-214