Wavelet transform based relay algorithm for the detection of stochastic high impedance faults

被引:28
作者
Lai, TM [1 ]
Snider, LA
Lo, E
机构
[1] Hong Kong Polytech Univ, Dept Elect Engn, Kowloon, Hong Kong, Peoples R China
[2] Tulane Univ, Dept Elect Engn & Comp Sci, New Orleans, LA 70118 USA
关键词
high impedance faults; wavelet transform; pattern recognition;
D O I
10.1016/j.epsr.2005.12.021
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
High impedance faults (HIF) are faults which are difficult to detect by overcurrent protection relays. This paper presents a practical pattern recognition based algorithm for electric distribution high impedance fault detection. The scheme recognizes the distortion of the voltage and current waveforms caused by the arcs usually associated with HIF The analysis using discrete wavelet transform (DWT) yields three phase voltage and current in the low frequency range which fed to a classifier for pattern recognition. The classifier is based on the algorithm using nearest neighbour rule approach. A HIF model was also developed, where the random nature of the arc was simulated using MATLAB. (c) 2006 Elsevier B.V. All rights reserved.
引用
收藏
页码:626 / 633
页数:8
相关论文
共 16 条
[1]  
[Anonymous], 1993, Ten Lectures of Wavelets
[2]  
[Anonymous], 2001, PATTERN CLASSIFICATI
[3]   DETECTION OF DISTRIBUTION HIGH IMPEDANCE FAULTS USING BURST NOISE SIGNALS NEAR 60 HZ [J].
AUCOIN, M ;
RUSSELL, BD .
IEEE TRANSACTIONS ON POWER DELIVERY, 1987, 2 (02) :342-348
[4]   A NEURAL NETWORK APPROACH TO THE DETECTION OF INCIPIENT FAULTS ON POWER DISTRIBUTION FEEDERS [J].
EBRON, S ;
LUBKEMAN, DL ;
WHITE, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (02) :905-914
[5]   HIGH IMPEDANCE FAULT ARCING ON SANDY SOIL IN 15KV DISTRIBUTION FEEDERS - CONTRIBUTIONS TO THE EVALUATION OF THE LOW-FREQUENCY SPECTRUM [J].
EMANUEL, AE ;
CYGANSKI, D ;
ORR, JA ;
SHILLER, S ;
GULACHENSKI, EM .
IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (02) :676-686
[6]   ANALYSIS OF HIGH-IMPEDANCE FAULT GENERATED SIGNALS USING A KALMAN FILTERING APPROACH [J].
GIRGIS, AA ;
CHANG, WB ;
MAKRAM, EB .
IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (04) :1714-1724
[7]   A PRACTICAL PROTECTIVE RELAY FOR DOWN-CONDUCTOR FAULTS [J].
JEERINGS, DI ;
LINDERS, JR .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (02) :565-574
[8]   CLASSIFICATION OF FAULTS AND SWITCHING EVENTS BY INDUCTIVE REASONING AND EXPERT SYSTEM METHODOLOGY [J].
KIM, CJ ;
RUSSELL, BD .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (03) :1631-1637
[9]   Analysis of distribution disturbances and arcing faults using the crest factor [J].
Kim, CJ ;
Russell, BD .
ELECTRIC POWER SYSTEMS RESEARCH, 1995, 35 (02) :141-148
[10]  
MAMISHEV AV, 1995, 1995 IEEE POWER INDUSTRY COMPUTER APPLICATION CONFERENCE, CONFERENCE PROCEEDINGS, P401, DOI 10.1109/PICA.1995.515270