A fast corrective load shedding control scheme to prevent AC/DC systems voltage collapse

被引:13
作者
Cai, Guanglin [1 ]
Zhang, Yongjun [1 ]
Chen, Rouyi [1 ]
Cai, Zexiang [1 ]
机构
[1] S China Univ Technol, Elect Power Coll, Guangzhou 510640, Guangdong, Peoples R China
来源
EUROPEAN TRANSACTIONS ON ELECTRICAL POWER | 2009年 / 19卷 / 06期
基金
中国国家自然科学基金;
关键词
load shedding; corrective control; voltage stability; voltage collapse; optimal multiplier power flow; linear programming; FAST COMPUTATION; MARGINS;
D O I
10.1002/etep.266
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a corrective load shedding algorithm to restore power flow solvability of AC/DC systems after severe contingencies. Firstly. contingency parameterization power flow is constructed to describe a set of multiple contingencies, including generators, HVDC links, ac lines and transformers. The post-contingency critical point is quickly determined through optimal multiplier power flow and a simple optimization-based outage parameter updating procedure. The updating strategy is better improved by the analysis of stability surface. At the nose point. the sensitivity analysis is performed to select the most effective control measure. Then, the corrective load shedding sensitivity-based linear programming model is constructed to improve the, stability margin. The numerical simulations on a practical 1621 bus system testify that the proposed method can prevent system from voltage collapse effectively and efficiently. Copyright (C) 2008 John Wiley & Sons, Ltd.
引用
收藏
页码:869 / 879
页数:11
相关论文
共 18 条
[11]   A POWER-FLOW MEASURE FOR UNSOLVABLE CASES [J].
OVERBYE, TJ .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1994, 9 (03) :1359-1365
[12]   LP-based OPF for corrective FACTS control to relieve overloads and voltage violations [J].
Shao, Wei ;
Vittal, Vijay .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (04) :1832-1839
[13]   Determination of load shedding for power-flow solvability using outage-continuation power flow (OCPF) [J].
Song, H. ;
Baik, S. -D. ;
Lee, B. .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2006, 153 (03) :321-325
[14]  
Van Cutsem T., 1998, VOLTAGE STABILITY EL, V441
[15]   Preventive/corrective control for voltage stability using direct interior point method [J].
Wang, X ;
Ejebe, GC ;
Tong, J ;
Waight, JG .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1998, 13 (03) :878-883
[16]   Fast computation of voltage stability security margins using nonlinear programming techniques [J].
Zarate, LAL ;
Castro, CA ;
Ramos, JLM ;
Ramos, ER .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (01) :19-27
[17]  
ZHAO J, 2005, IEEE POW ENG SOC GEN
[18]  
ZHAO J, 2006, IEEE POW ENG SOC GEN