Aerodynamic analysis and CFD simulation of several cellulose evaporative cooling pads used in Mediterranean greenhouses

被引:65
作者
Franco-Salas, Antonio [2 ]
Valera, D. L. [1 ]
Pena, A. [1 ]
Perez, A. M. [2 ]
机构
[1] Univ Almeria, Ctra Sacramento S-N, Almeria 04120, Spain
[2] Univ Seville, ETSIA, Seville 41013, Spain
关键词
Greenhouse; Aerodynamic analysis; CFD; Evaporative cooling; Fan and pad; Pressure drop; INSECT-PROOF SCREENS; AIR-FLOW; NATURAL VENTILATION; TEMPERATURE; PERFORMANCE; SYSTEM; HUMIDITY; WATER;
D O I
10.1016/j.compag.2011.01.019
中图分类号
S [农业科学];
学科分类号
09 ;
摘要
The present work makes an aerodynamic analysis and computational fluid dynamics (CFD) simulation of the four commercial models of corrugated cellulose evaporative cooling pads that are most widely used in Mediterranean greenhouses. The geometric characteristics of the pads have been determined as well as the volume of water they retain at different flows of water, thus obtaining the mean thickness of the sheet of water which runs down them and their porosity. By means of low velocity wind tunnel experiments, the pressure drop produced by the pads has been recorded at different wind speeds and water flows. In this way it has been possible to obtain the relationship of the permeability and the inertial factor with pad porosity using a cubic type equation. Finally, a CFD simulation with a 3D model has been carried out for both dry pads (Q(w) = 0 l s(-1) m(-2)) and wet ones (Q(w) = 0.256 l s(-1) m(-2)), finding good correlation between the simulated and experimental pressure drop, with maximum differences of 9.08% for dry pads and 15.53% for wet ones at an airspeed of 3 m s(-1). (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:218 / 230
页数:13
相关论文
共 53 条
  • [21] Performance improvement of gas turbines of Fars (Iran) combined cycle power plant by intake air cooling using a media evaporative cooler
    Hosseini, R.
    Beshkani, A.
    Soltani, M.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (04) : 1055 - 1064
  • [22] Response of an eggplant crop grown under Mediterranean summer conditions to greenhouse fog cooling
    Katsoulas, N.
    Savvas, D.
    Tsirogiannis, I.
    Merkouris, O.
    Kittas, C.
    [J]. SCIENTIA HORTICULTURAE, 2009, 123 (01) : 90 - 98
  • [23] Analysis of greenhouse ventilation efficiency based on computational fluid dynamics
    Khaoua, S. A. Ould
    Bournet, P. E.
    Migeon, C.
    Boulard, T.
    Chasseriaux, G.
    [J]. BIOSYSTEMS ENGINEERING, 2006, 95 (01) : 83 - 98
  • [24] 3-D CFD analysis of relative humidity distribution in greenhouse with a fog cooling system and refrigerative dehumidifiers
    Kim, Keesung
    Yoon, Jeong-Yeol
    Kwon, Hyuck-Jin
    Han, Jin-Hee
    Son, Jung Eek
    Nam, Sang-Woon
    Giacomelli, Gene A.
    Lee, In-Bok
    [J]. BIOSYSTEMS ENGINEERING, 2008, 100 (02) : 245 - 255
  • [25] Temperature gradients in a partially shaded large greenhouse equipped with evaporative cooling pads
    Kittas, C
    Bartzanas, T
    Jaffrin, A
    [J]. BIOSYSTEMS ENGINEERING, 2003, 85 (01) : 87 - 94
  • [26] Koca R. W., 1991, Applied Engineering in Agriculture, V7, P485
  • [27] LEE LB, 2006, ACTA HORTIC, V719, P341
  • [28] Wind tunnel modeling the system performance of alternative evaporative cooling pads in Taiwan region
    Liao, CM
    Chiu, KH
    [J]. BUILDING AND ENVIRONMENT, 2002, 37 (02) : 177 - 187
  • [29] Lopez A, 2010, T ASABE, V53, P945
  • [30] Airflow and microclimate patterns in a one-hectare Canary type greenhouse: An experimental and CFD assisted study
    Majdoubi, H.
    Boulard, T.
    Fatnassi, H.
    Bouirden, L.
    [J]. AGRICULTURAL AND FOREST METEOROLOGY, 2009, 149 (6-7) : 1050 - 1062