On the bidirectional flow across an atrium ceiling vent

被引:17
作者
Chow, W. K. [1 ]
Li, J. [2 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Area Strength Fire Safety Engn, Res Ctr Fire Engn, Kowloon, Hong Kong, Peoples R China
[2] Beijing Univ Technol, Coll Architecture & Civil Engn, Beijing 100124, Peoples R China
关键词
Horizontal ceiling vent; Bidirectional flow; Pressure drop; Smoke exhaust; SMALL OPENINGS; BUOYANCY;
D O I
10.1016/j.buildenv.2011.06.018
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Sizing of horizontal ceiling vent in a tall atrium is usually based on vent flow models with unidirectional flow. This is only good for natural vents with large pressure differences between inside and outside. For low pressure differential across the horizontal ceiling vent as experienced in some atrium fires, bidirectional smoke flow rates were observed. The extraction rate through the vent would be reduced, giving poor performance of the smoke exhaust system. Bidirectional flow across a ceiling vent will be discussed in this paper. Models available in the literature will be briefly reviewed first. A new model was developed on studying effects of bidirectional flow across a horizontal vent on the smoke layer interface height. A critical pressure difference between inside and outside across the vent can be estimated on inducing bidirectional flows. The approach is illustrated with an example sizing calculation for a cubic atrium commonly found in Hong Kong. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:2598 / 2602
页数:5
相关论文
共 24 条
[1]   AN ANALYTICAL MODEL ON STATIC SMOKE EXHAUST IN ATRIA [J].
Chow, Cheuk Lun ;
Li, Junmei .
JOURNAL OF CIVIL ENGINEERING AND MANAGEMENT, 2010, 16 (03) :372-381
[2]  
CHOW CL, 2010, INT J VENTILATION, V8
[3]   Buoyancy and inertial force on oscillations of thermal-induced convective flow across a vent [J].
Chow, W. K. ;
Gao, Y. .
BUILDING AND ENVIRONMENT, 2011, 46 (02) :315-323
[4]   Oscillating behaviour of fire-induced air flow through a ceiling vent [J].
Chow, W. K. ;
Gao, Y. .
APPLIED THERMAL ENGINEERING, 2009, 29 (16) :3289-3298
[5]  
Chow W.K., 2004, ASHRAE T, V110, P479
[6]  
CHOW WK, 2005, INT J ENG PERFORMANC, V7, P8
[7]  
Cooper L.Y., 1994, 5384 NISTIR
[8]  
Cooper L.Y., 2002, SFPE HDB FIRE PROTEC, Vthird
[9]   COMBINED BUOYANCY AND PRESSURE-DRIVEN FLOW-THROUGH A SHALLOW, HORIZONTAL, CIRCULAR VENT [J].
COOPER, LY .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1995, 117 (03) :659-667
[10]  
COOPER LY, 1990, 4402 NISTIR