Experimental study of an air-source heat pump for simultaneous heating and cooling - Part 2: Dynamic behaviour and two-phase thermosiphon defrosting technique

被引:50
作者
Byrne, Paul [1 ]
Miriel, Jacques [1 ]
Lenat, Yves [1 ]
机构
[1] Univ Rennes 1, Univ Europeenne Bretagne, Equipe MTRheo, Lab LGCGM,INSA Rennes,IUT Genie Civil, F-35704 Rennes 7, France
关键词
Heat pump; Heating; Cooling; Thermosiphon; Defrosting; PERFORMANCE; TUBE;
D O I
10.1016/j.apenergy.2011.03.002
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This article presents the concepts of an air-source heat pump for simultaneous heating and cooling (HPS) designed for hotels and smaller residential, commercial and office buildings in which simultaneous needs in heating and cooling are frequent. The main advantage of the HPS is to carry out simultaneously space heating and space cooling with the same energy input. Ambient air is used as a balancing source to run a heating or a cooling mode. The second advantage is that, during winter, energy recovered by the subcooling of the refrigerant is stored at first in a water tank and used subsequently as a cold source at the water evaporator to improve the average performance and to carry out defrosting of the air evaporator using a two-phase thermosiphon. Unlike conventional air-source heat pumps, defrosting is carried out without stopping the heat production. A R407C HPS prototype was built and tested. The basic concepts of the HPS are detailed in part1 of this article [1]. Its performance on defined operating conditions corresponds to the data given by the selection software of the compressor manufacturer. In the present part of this article, the operation of the high pressure control system, the transitions between heating, cooling and simultaneous modes and the defrosting sequence are analysed and validated experimentally. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:3072 / 3078
页数:7
相关论文
共 14 条
[1]   Experimental study of an air-source heat pump for simultaneous heating and cooling - Part 1: Basic concepts and performance verification [J].
Byrne, Paul ;
Miriel, Jacques ;
Lenat, Yves .
APPLIED ENERGY, 2011, 88 (05) :1841-1847
[2]   Design and simulation of a heat pump for simultaneous heating and cooling using HFC or CO2 as a working fluid [J].
Byrne, Paul ;
Miriel, Jacques ;
Lenat, Yves .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (07) :1711-1723
[3]   Simulation of the two-phase flow in a thermosyphon using an inclined transparent tube with the lower-end closed and the upper-end open [J].
Dobson, RT .
REVUE GENERALE DE THERMIQUE, 1998, 37 (11) :968-972
[4]   Prediction of temperature profiles using artificial neural networks in a vertical thermosiphon reboiler [J].
Hakeem, M. A. ;
Kamil, M. ;
Arman, I. .
APPLIED THERMAL ENGINEERING, 2008, 28 (13) :1572-1579
[5]   Comparison between hot-gas bypass defrosting and reverse-cycle defrosting methods on an air-to-water heat pump [J].
Huang, Dong ;
Li, Quanxu ;
Yuan, Xiuling .
APPLIED ENERGY, 2009, 86 (09) :1697-1703
[6]  
*IIF IIR, 2001, R407C IFF IIR
[7]   A study on the performance enhancement of heat pump using electric heater under the frosting condition: Heat pump under frosting condition [J].
Kwak, Kyungmin ;
Bai, Cheolho .
APPLIED THERMAL ENGINEERING, 2010, 30 (6-7) :539-543
[8]   Experimental study on the double-evaporator thermosiphon for cooling HTS (high temperature superconductor) system [J].
Lee, Junghyun ;
Ko, Junseok ;
Kim, Youngkwon ;
Jeong, Sangkwon ;
Sung, Taehyun ;
Han, Younghee ;
Lee, Jeong-Phil ;
Jung, Seyong .
CRYOGENICS, 2009, 49 (08) :390-397
[9]   Control strategy and experimental study on a novel defrosting method for air-source heat pump [J].
Liang, Cai-Hua ;
Zhang, Xiao-Song ;
Li, Xiu-Wei ;
Chen, Zhen-Qian .
APPLIED THERMAL ENGINEERING, 2010, 30 (8-9) :892-899
[10]   Frosting of heat pump with heat recovery facility [J].
Liu, Di ;
Zhao, Fu-Yun ;
Tang, Guang-Fa .
RENEWABLE ENERGY, 2007, 32 (07) :1228-1242