New method for detecting low current faults in electrical distribution systems

被引:48
作者
Zamora, I. [1 ]
Mazon, A. J.
Sagastabeitia, K. J.
Zamora, J. J.
机构
[1] Univ Basque Country, Dept Elect Engn, E-48013 Bilbao, Spain
[2] Univ Basque Country, Dept Elect & Telecommun Engn, E-48013 Bilbao, Spain
关键词
distribution systems; fault diagnosis; grounding; low current faults; signal superposition;
D O I
10.1109/TPWRD.2007.905273
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In electrical distribution systems, low current faults may be caused by a high impedance fault or by the fault current limitation caused by the neutral to ground connection. In the former case, an indirect contact or insulation degradation give a high value of the fault impedance. In the latter, the neutral grounding may be either isolated or compensated. Nevertheless, these types of faults do not produce enough current so that the traditional overcurrent relays or fuses are not able to detect the fault., This paper presents a new methodology, based on the super-position of voltage signals of certain frequency, for the detection of low current single phase faults in radial distribution systems. The simulation analysis and laboratory tests carried out have proved the validity of the methodology for any type of grounding method.
引用
收藏
页码:2072 / 2079
页数:8
相关论文
共 16 条
[1]   Directional ground-fault indicator for high-resistance grounded systems [J].
Baldwin, T ;
Renovich, F ;
Saunders, LF .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2003, 39 (02) :325-332
[2]  
DRUML JG, 1996, 12656534 REE, P68
[3]  
*HD COMSYS LTD TIM, RIPL CONTR SYST LOAD
[4]   Fuzzy detection of high impedance faults in radial distribution feeders [J].
Jota, PRS ;
Jota, FG .
ELECTRIC POWER SYSTEMS RESEARCH, 1999, 49 (03) :169-174
[5]  
Ko JH, 1998, IEEE CONF R, P399, DOI 10.1109/EMPD.1998.702585
[6]   High-impedance fault detection using discrete wavelet transform and frequency range and RMS conversion [J].
Lai, TM ;
Snider, LA ;
Lo, E ;
Sutanto, D .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) :397-407
[7]   Evaluation of a new proposal for an arcing fault detection method based on wavelet packet analysis [J].
Lazkano, A ;
Ruiz, J ;
Aramendi, E ;
Leturiondo, LA .
EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2004, 14 (03) :161-174
[8]  
Leitloff V, 1997, EUR T ELECTR POWER, V7, P65, DOI 10.1002/etep.4450070110
[9]   Electronic circuits tests in laboratory for superimposing voltages techniques [J].
Mazón, AJ ;
Zamora, JJ ;
Zamora, I ;
Albizu, I ;
Diez, M .
MELECON 2004: PROCEEDINGS OF THE 12TH IEEE MEDITERRANEAN ELECTROTECHNICAL CONFERENCE, VOLS 1-3, 2004, :995-998
[10]   DSTRP:: A new algorithm for high impedance fault detection in compensated neutral grounded MV power systems [J].
Ruz, F ;
Quijano, A ;
Gómez, E .
EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2003, 13 (01) :23-28