Wind tunnel tests on compartment fires with crossflow ventilation

被引:40
作者
Chen, H. X. [2 ]
Liu, N. A. [2 ]
Chow, W. K. [1 ]
机构
[1] Hong Kong Polytech Univ, Res Ctr Fire Engn, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
[2] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230026, Anhui, Peoples R China
关键词
Compartment fire; Wind; Cross ventilation; HEAT FLUXES; ENCLOSURE; SMOKE; VENT;
D O I
10.1016/j.jweia.2011.07.006
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
When a fire occurs in a room at ground level or a compartment located in the higher floors of a very tall building, the strong ambient wind will play an important role in fire spreading and smoke movement behavior. However, wind effect on compartment fire in cross ventilation condition has not been fully studied so far. In the present study, an effort has been made to study the wind effect on compartment fire in cross ventilation condition through experimental investigations. The experimental fire was generated by 250 ml n-heptane on the floor center of a cube enclosure with two opposite vents on the walls. The inside and outside gas temperature profiles at different vertical and horizontal locations were recorded by two thermocouple matrixes. The ambient wind velocity was set to 0, 1.5 and 3 m s(-1). It is observed that the ambient wind would enhance the fire severity by increasing the compartment fire temperature and reducing the time to flashover. The spilled-out flame/plume would extend horizontally farther with the increase of wind speed. Simple theoretical analysis shows that there is a critical wind velocity, or a dimensional number, to differentiate whether the gas flow across the vents is bidirectional or unidirectional, which is believed to influence enclosure fire behavior greatly. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1025 / 1035
页数:11
相关论文
共 15 条
[1]  
Drysdale D., 1999, An Introduction to Fire Dynamics, Vsecond
[2]   Post-flashover fires for structural design [J].
Feasey, R ;
Buchanan, A .
FIRE SAFETY JOURNAL, 2002, 37 (01) :83-105
[3]  
Jaluria Y, 1995, COMBUST SCI TECHNOL, V111, P197
[4]  
Kawagoe K., 1958, FIRE BEHAV ROOMS
[5]   Compartment fires: CALTREE and cross-ventilation [J].
Kumar, Rajiv ;
Naveen, M. .
COMBUSTION SCIENCE AND TECHNOLOGY, 2007, 179 (08) :1549-1567
[6]   An experimental fire in compartment with dual vent on opposite walls [J].
Kumar, Rajiv ;
Naveen, M. .
COMBUSTION SCIENCE AND TECHNOLOGY, 2007, 179 (08) :1527-1547
[7]   Heat fluxes and flame heights in facades from fires in enclosures of varying geometry [J].
Lee, Yee-Ping ;
Delichatsios, Michael A. ;
Silcock, G. W. H. .
PROCEEDINGS OF THE COMBUSTION INSTITUTE, 2007, 31 :2521-2528
[8]   Heat fluxes on opposite building wall by flames emerging from an enclosure [J].
Lee, Yee-Ping ;
Delichatsios, M. A. ;
Ohmiya, Yoshifumi ;
Wakatsuki, Kaoru ;
Yanagisawa, Akito ;
Goto, Daisuke .
PROCEEDINGS OF THE COMBUSTION INSTITUTE, 2009, 32 :2551-2558
[9]   On the operation time of horizontal ceiling vent in an atrium [J].
Li, YZ ;
Huo, R ;
Chow, WK .
JOURNAL OF FIRE SCIENCES, 2002, 20 (01) :37-51
[10]   Experimental study of natural roof ventilation in full-scale enclosure fire tests in a small compartment [J].
Merci, Bart ;
Vandevelde, Paul .
FIRE SAFETY JOURNAL, 2007, 42 (08) :523-535