Maximum Frequency Deviation Calculation in Small Isolated Power Systems

被引:138
作者
Egido, Ignacio [1 ]
Fernandez-Bernal, Fidel [1 ]
Centeno, Pablo [2 ]
Rouco, Luis [1 ]
机构
[1] Univ Pontificia Comillas Madrid, Escuela Tecn Super Ingn ICAI, Madrid, Spain
[2] Alstom Power Syst, Baden, Switzerland
关键词
Frequency deviation; isolated power systems; load shedding; minimum frequency; spinning reserve; DYNAMIC-MODELS; BOILER; PLANT;
D O I
10.1109/TPWRS.2009.2030399
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Large frequency deviations due to a number of disturbances are frequent in small isolated power systems. The maximum frequency deviation in the system is limited to prevent other generator tripping. It is important to have an accurate model to calculate it, both for system planning and operation. A new simplified model to calculate the maximum frequency deviation when either a generator or load-related disturbance occurs in these systems is presented. This model takes into account the response of governor-prime mover even when different technologies are present in the power system. Model parameters can be easily obtained from either more complex models or from test records. Simulation results for an actual power system aimed at checking the model accuracy are presented. High accuracy is obtained while computation time is reduced due to the simplicity of the model.
引用
收藏
页码:1731 / 1738
页数:8
相关论文
共 21 条
[11]   A model of fossil fueled plant with once-through boiler for power system frequency simulation studies [J].
Inoue, T ;
Taniguchi, H ;
Ikeguchi, Y .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2000, 15 (04) :1322-1328
[12]   POWER-PLANT MODELS FOR OPERATOR TRAINING SIMULATORS [J].
KOLA, V ;
BOSE, A ;
ANDERSON, PM .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1989, 4 (02) :559-565
[13]  
Kundur P., 1994, POWER SYSTEM STABILI
[14]   FREQUENCY ACTUATED LOAD SHEDDING AND RESTORATION .1. PHILOSOPHY [J].
MALISZEWSKI, RM ;
DUNLOP, RD ;
WILSON, GL .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1971, PA90 (04) :1452-+
[15]   New thermal governor model selection and validation in the WECC [J].
Pereira, L ;
Kosterev, D ;
Davies, D ;
Patterson, S .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2004, 19 (01) :517-523
[16]   A new thermal governor modeling approach in the WECC [J].
Pereira, L ;
Undrill, J ;
Kosterev, D ;
Davies, D ;
Patterson, S .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2003, 18 (02) :819-829
[17]  
*POW TECHN INC, 2002, PSS E 29 ONL DOC
[18]   SIMPLIFIED MATHEMATICAL REPRESENTATIONS OF HEAVY-DUTY GAS-TURBINES [J].
ROWEN, WI .
JOURNAL OF ENGINEERING FOR POWER-TRANSACTIONS OF THE ASME, 1983, 105 (04) :865-869
[19]   Adaptive underfrequency load shedding based on the magnitude of the disturbance estimation [J].
Terzija, Vladimir V. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (03) :1260-1266
[20]   Self-healing in power systems: An approach using islanding and rate of frequency decline-based load shedding [J].
You, H ;
Vittal, V ;
Yang, Z .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2003, 18 (01) :174-181