Night ventilation control strategies in office buildings

被引:58
作者
Wang, Zhaojun [1 ]
Yi, Lingli [1 ]
Gao, Fusheng [1 ]
机构
[1] Harbin Inst Technol, Sch Municipal & Environm Engn, Harbin 150090, Peoples R China
关键词
Control strategy; Mechanical night ventilation; Parameter analyses; Energy efficiency; Cold climate; DESIGN; SUMMER; MASS;
D O I
10.1016/j.solener.2009.07.003
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In moderate climates night ventilation is an effective and energy-efficient approach to improve the indoor thermal environment for office buildings during the summer months, especially for heavyweight construction. However, is night ventilation a suitable strategy for office buildings with lightweight construction located in cold climates? In order to answer this question, the whole energy-consumption analysis software EnergyPlus was used to simulate the indoor thermal environment and energy consumption in typical office buildings with night mechanical ventilation in three cities in northern China. The summer outdoor climate data was analyzed, and three typical design days were chosen. The most important factors influencing night ventilation performance such as ventilation rates, ventilation duration, building mass and climatic conditions were evaluated. When night ventilation operation time is closer to active cooling time, the efficiency of night ventilation is higher. With night ventilation rate of 10 ach, the mean radiant temperature of the indoor surface decreased by up to 3.9 degrees C. The longer the duration of operation, the more efficient the night ventilation strategy becomes. The control strategies for three locations are given in the paper. Based on the optimized strategies, the operation consumption and fees are calculated. The results show that more energy is saved in office buildings cooled by a night ventilation system in northern China than ones that do not employ this strategy. (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1902 / 1913
页数:12
相关论文
共 24 条
[1]  
[Anonymous], 1972, P S THERMAL COMFORT
[2]   Parameter study on performance of building cooling by night-time ventilation [J].
Artmann, N. ;
Manz, H. ;
Heiselberg, P. .
RENEWABLE ENERGY, 2008, 33 (12) :2589-2598
[3]  
*ASHRAE INC, 552004 ASHRAE INC
[4]   Night ventilation for building cooling in summer [J].
Blondeau, P ;
Sperandio, M ;
Allard, F .
SOLAR ENERGY, 1997, 61 (05) :327-335
[5]   Passive cooling in a low-energy office building [J].
Breesch, H ;
Bossaer, A ;
Janssens, A .
SOLAR ENERGY, 2005, 79 (06) :682-696
[6]  
CAO S, 1999, BUILDING ENERGY ENV, V18, P12
[7]  
CHEN Z, 1993, BUILDING ENERGY ENV, V12, P44
[8]  
*CIBSE, 2000, GUID H
[9]   Sensitivity analysis of a maritime located night ventilated library building [J].
Finn, Donal P. ;
Connolly, Darragh ;
Kenny, Paul .
SOLAR ENERGY, 2007, 81 (06) :697-710
[10]  
Fletcher J., 1996, NIGHT COOLING CONTRO