Experimental investigation on vapor injection heat pump with a newly designed twin rotary variable speed compressor for cold regions

被引:70
作者
Yan, Gang [1 ]
Jia, Qinglei [1 ]
Bai, Tao [1 ]
机构
[1] Xi An Jiao Tong Univ, Dept Refrigerat & Cryogen Engn, Sch Energy & Power Engn, Xian 710049, Peoples R China
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2016年 / 62卷
关键词
Experiment; Heat pump air conditioner; Vapor injection; Twin rotary compressor; Heating performance; Variable speed; SCROLL COMPRESSOR; PERFORMANCE; SIMULATION; SYSTEM; CYCLE; MODEL;
D O I
10.1016/j.ijrefrig.2015.10.024
中图分类号
O414.1 [热力学];
学科分类号
摘要
A newly designed twin rotary variable speed compressor was adopted to improve the heating performance of a vapor injection heat pump air conditioner (HPAC) at cold regions in this study. The performances of a R410A HPAC were measured and investigated. The results showed that an optimum intermediate pressure existed to achieve the maximum heating capacity and system COP for the injection cycle, and the heating capacity was enhanced effectively by increasing compressor frequency, however, at the cost of COP decrease. Comparative research on system performances between injection and non-injection cycles indicated that the newly designed compressor could improve the heating performance of the HPAC at low ambient temperatures. Specifically, the system's heating capacity was enhanced by 5.6%-14.4%, and COP improvement reached up to 3.5%. Vapor injection cycle was not suggested at high ambient temperatures due to its lower COP compared with non-injection cycles. (C) 2016 Elsevier Ltd and International Institute of Refrigeration. All rights reserved.
引用
收藏
页码:232 / 241
页数:10
相关论文
共 23 条
[1]   Energy Savings through Variable Speed Compressor Heat Pump Systems [J].
Adhikari, R. S. ;
Aste, N. ;
Manfren, M. ;
Marini, D. .
2011 2ND INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY ENGINEERING (ICAEE), 2012, 14 :1337-1342
[2]  
AQSIQ (China Administration of Quality Supervision Inspection and Quarantine), 2004, GBT7725 AQSIQ CHIN A
[3]   Performance characteristics of a two-stage CO2 heat pump water heater adopting a sub-cooler vapor injection cycle at various operating conditions [J].
Baek, Changhyun ;
Heo, Jaehyeok ;
Jung, Jongho ;
Cho, Honghyun ;
Kim, Yongchan .
ENERGY, 2014, 77 :570-578
[4]   Development and performance of a dual tank solar-assisted heat pump system [J].
Banister, Carsen J. ;
Collins, Michael R. .
APPLIED ENERGY, 2015, 149 :125-132
[5]   Investigation of the heat pump water heater using economizer vapor injection system and mixture of R22/R600a [J].
Cao Feng ;
Wang Kai ;
Wang Shouguo ;
Xing Ziwen ;
Shu Pencheng .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (03) :509-514
[6]   Semi-empirical modelling of a variable speed scroll compressor with vapour injection [J].
Dardenne, Laurent ;
Fraccari, Enrico ;
Maggioni, Alessandro ;
Molinaroli, Luca ;
Proserpio, Luca ;
Winandy, Eric .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 54 :76-87
[7]   Comparison of the heating performance of air-source heat pumps using various types of refrigerant injection [J].
Heo, Jaehyeok ;
Jeong, Min Woo ;
Baek, Changhyun ;
Kim, Yongchan .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (02) :444-453
[8]   Effects of flash tank vapor injection on the heating performance of an inverter-driven heat pump for cold regions [J].
Heo, Jaehyeok ;
Jeong, Min Woo ;
Kim, Yongchan .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (04) :848-855
[9]   A review of heat pump water heating systems [J].
Hepbasli, Arif ;
Kalinci, Yildiz .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2009, 13 (6-7) :1211-1229
[10]   Reversible heat pump model for seasonal performance optimization [J].
Kinab, Elias ;
Marchio, Dominique ;
Riviere, Philippe ;
Zoughaib, Assaad .
ENERGY AND BUILDINGS, 2010, 42 (12) :2269-2280