Theoretical research of a silica gel-water adsorption chiller in a micro combined cooling, heating and power (CCHP) system

被引:96
作者
Li, S. [1 ]
Wu, J. Y. [1 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
基金
中国国家自然科学基金;
关键词
Adsorption system; Micro CCHP; Model; COP; Performance; PUMP; TEMPERATURE; DESIGN;
D O I
10.1016/j.apenergy.2008.09.016
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A novel micro CCHP system, which is based on a two bed silica gel-water adsorption chiller, is constructed in this work. To reveal the chiller characteristic in this system, a transient model of the adsorption chiller is developed. According to the comparison of the simulated results and experimental data, the presented model shows a good performance in predicting the chiller performance, with both stable and variable heat source temperature. With the analysis of simulated results, it is found that the cooling capacity and the coefficient of performance (COP) of the chiller are influenced significantly by the average value and variation rate of electric load, as well as the average value of cooling load. The water tank also shows a great effect on the chiller performance. To get better performance of the chiller, the water tank should be adopted when the electric load is low or its variation rate is positive, and should not be utilized when the electric load is high or its variation rate is negative. A 500 L water tank is recommended in order to get better performance and acceptable start-up time. Furthermore, to get better performance as well as higher security, a cold accumulator should be adopted. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:958 / 967
页数:10
相关论文
共 18 条
[1]   Solar air conditioning in Europe - an overview [J].
Balaras, Constantinos A. ;
Grossman, Gershon ;
Henning, Hans-Martin ;
Infante Ferreira, Carlos A. ;
Podesser, Erich ;
Wang, Lei ;
Wiemken, Edo .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2007, 11 (02) :299-314
[2]   Micro-combined heat and power in residential and light commercial applications [J].
d'Accadia, MD ;
Sasso, M ;
Sibilio, S ;
Vanoli, L .
APPLIED THERMAL ENGINEERING, 2003, 23 (10) :1247-1259
[3]   Theoretical and experimental study on characteristics of a novel silica gel-water chiller under the conditions of variable heat source temperature [J].
Di, J. ;
Wu, J. Y. ;
Xia, Z. Z. ;
Wang, R. Z. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (03) :515-526
[4]   Solar refrigeration options - a state-of-the-art review [J].
Kim, D. S. ;
Ferreira, C. A. Infante .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (01) :3-15
[5]   Feasibility of a new domestic CHP trigeneration with heat pump:: I.: Design and development [J].
Míguez, JL ;
Murillo, S ;
Porteiro, J ;
López, LM .
APPLIED THERMAL ENGINEERING, 2004, 24 (10) :1409-1419
[6]   Effect of heat-saving measures on the CO2 savings attributable to micro-combined heat and power (μCHP) systems in UK dwellings [J].
Peacock, A. D. ;
Newborough, M. .
ENERGY, 2008, 33 (04) :601-612
[7]   Environmental impacts of distributed energy systems - The case of micro cogeneration [J].
Pehnt, Martin .
ENVIRONMENTAL SCIENCE & POLICY, 2008, 11 (01) :25-37
[8]   Performance evaluation of a low-temperature waste heat driven multi-bed adsorption chiller [J].
Saha, BB ;
Koyama, S ;
Lee, JB ;
Kuwahara, K ;
Alam, KCA ;
Hamamoto, Y ;
Akisawa, A ;
Kashiwagi, T .
INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 2003, 29 (08) :1249-1263
[9]  
SHEN WD, 2001, ENG THERMODYNAMICS, P232
[10]   Domestic-scale combined heat-and-power system incorporating a heat pump: analysis of a prototype plant [J].
Smith, MA ;
Few, PC .
APPLIED ENERGY, 2001, 70 (03) :215-232