Measures against the adverse impact of natural wind on air-cooled condensers in power plant

被引:37
作者
Yang LiJun [1 ]
Du XiaoZe [1 ]
Yang YongPing [1 ]
机构
[1] N China Elect Power Univ, Minist Educ China, Key Lab Condit Monitoring & Control Power Plant E, Beijing 102206, Peoples R China
关键词
air-cooled condenser; wind speed and direction; flow and heat transfer; back pressure; power plant; HEAT-EXCHANGERS; TUNNEL SIMULATION; FAN PERFORMANCE; FLOW LOSSES; RECIRCULATION; INLET;
D O I
10.1007/s11431-010-0094-4
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The natural wind plays disadvantageous roles in the operation of air-cooled steam condensers in power plant. It is of use to take various measures against the adverse effect of wind for the performance improvement of air-cooled condensers. Based on representative 2x600 MW direct air-cooled power plant, three ways that can arrange and optimize the flow field of cooling air thus enhance the heat transfer of air-cooled condensers were proposed. The physical and mathematical models of air-cooled condensers with various flow leading measures were presented and the flow and temperature fields of cooling air were obtained by CFD simulation. The back pressures of turbine were calculated for different measures on the basis of the heat transfer model of air-cooled condensers. The results show that the performance of air-cooled condensers is improved thus the back pressure of turbine is lowered to some extent by taking measures against the adverse impact of natural wind.
引用
收藏
页码:1320 / 1327
页数:8
相关论文
共 14 条
[1]   Numerical investigation of fan performance in a forced draft air-cooled steam condenser [J].
Bredell, JR ;
Kröger, DG ;
Thiart, GD .
APPLIED THERMAL ENGINEERING, 2006, 26 (8-9) :846-852
[2]  
DING EM, 1992, AIR COOLED TECHNOLOG
[3]   Flow distortions at the fan inlet of forced-draught air-cooled heat exchangers [J].
Duvenhage, K ;
Vermeulen, JA ;
Meyer, CJ ;
Kroger, DG .
APPLIED THERMAL ENGINEERING, 1996, 16 (8-9) :741-752
[4]   The influence of wind on the performance of forced draught air-cooled heat exchangers [J].
Duvenhage, K ;
Kroger, DG .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 1996, 62 (2-3) :259-277
[5]   Wind tunnel simulation on re-circulation of air-cooled condensers of a power plant [J].
Gu, ZF ;
Li, H ;
Zhang, WH ;
Li, Y ;
Peng, JY .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2005, 93 (06) :509-520
[6]   Wind tunnel simulation of exhaust recirculation in an air-cooling system at a large power plant [J].
Gu, Zhifu ;
Chen, Xuerei ;
Lubitz, William ;
Li, Yan ;
Luo, Wonlin .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2007, 46 (03) :308-317
[7]   Numerical investigation into the effect of cross-flow on the performance of axial flow fans in forced draught air-cooled heat exchangers [J].
Hotchkiss, PJ ;
Meyer, CJ ;
von Backström, TW .
APPLIED THERMAL ENGINEERING, 2006, 26 (2-3) :200-208
[8]   Numerical investigation of hot air recirculation of air-cooled condensers at a large power plant [J].
Liu, Peiqing ;
Duan, Huishen ;
Zhao, Wanli .
APPLIED THERMAL ENGINEERING, 2009, 29 (10) :1927-1934
[9]   Numerical investigation of the effect of fan performance on forced draught air-cooled heat exchanger plenum chamber aerodynamic behaviour [J].
Meyer, CJ ;
Kröger, DG .
APPLIED THERMAL ENGINEERING, 2004, 24 (2-3) :359-371
[10]   Plenum chamber flow losses in forced draught air-cooled heat exchangers [J].
Meyer, CJ ;
Kroger, DG .
APPLIED THERMAL ENGINEERING, 1998, 18 (9-10) :875-893