DSP Based Implementation of a Three-Phase Four-Wire DSTATCOM for Voltage Regulation and Power Quality Improvement

被引:6
作者
Jayaprakash, P. [1 ]
Singh, Bhim [2 ]
Kothari, D. P. [3 ]
机构
[1] Indian Inst Technol, Ctr Energy Studies, Hauz Khas, New Delhi 110016, India
[2] Indian Inst Technol, Dept Elect Engn, New Delhi 110016, India
[3] Vellore Inst Technol, Vellore 632014, Tamil Nadu, India
来源
IECON: 2009 35TH ANNUAL CONFERENCE OF IEEE INDUSTRIAL ELECTRONICS, VOLS 1-6 | 2009年
关键词
Power Quality Improvement; Three-Phase Four-Wire DSTATCOM; Three-Leg Voltage Source Converter; Star/Delta Transformer; Neutral Current Compensation;
D O I
10.1109/IECON.2009.5415140
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A three-phase four-wire DSTATCOM (distribution static compensator) based on three-leg VSC (voltage source converter) and a star/delta transformer is proposed for voltage regulation in a three-phase four-wire distribution system. The DSTATCOM is controlled to compensate reactive power, eliminate harmonic currents, balances the load and also to mitigate the neutral current. The use of star/delta transformer for interfacing to a three-phase four-wire power distribution system reduces required rating of the VSC for a three-phase four-wire DSTATCOM. The IGBT (insulated gate bipolar transistor) based VSC is capacitor supported and is controlled for the required compensation of the load current. The dc bus voltage of the VSC is regulated during varying load conditions. The control algorithm is based on synchronous reference frame (SRF) theory for generating the gating pulses. The performance of the three-phase four-wire DSTATCOM is validated for voltage regulation along with neutral current compensation, harmonic elimination and balancing of linear loads as well as non-linear loads through hardware implementation using dSPACE, which is based on DS1104 R&D controller and a slave DSP subsystem based on TMS320F240.
引用
收藏
页码:3484 / +
页数:2
相关论文
共 16 条
[1]  
Akagi H., 2007, INSTANTANEOUS POWER
[2]  
[Anonymous], 2014, 5192014 IEEE
[3]  
Dugan RC, 2006, ELECT POWER SYSTEMS
[4]  
Fuchs EF, 2008, POWER QUALITY IN POWER SYSTEMS AND ELECTRICAL MACHINES, P1
[5]   Voltage-regulation performance of a shunt active filter intended for installation on a power distribution system [J].
Fujita, Hideaki ;
Akagi, Hirofumi .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2007, 22 (03) :1046-1053
[6]  
Ghosh A., 2002, POWER QUALITY ENHANC
[7]  
HURNGLIAHNG, 2008, IEEE T POWER ELECTR, V23, P252
[8]   Novel power converter topology for three-phase four-wire hybrid power filter [J].
Jou, H. -L. ;
Wu, K. -D. ;
Wu, J. -C. ;
Li, C. -H. ;
Huang, M. -S. .
IET POWER ELECTRONICS, 2008, 1 (01) :164-173
[9]   Analysis of Zig-Zag transformer applying in the three-phase four-wire distribution power system [J].
Jou, HL ;
Wu, JC ;
Wu, KD ;
Chiang, WJ ;
Chen, YH .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :1168-1173
[10]  
KIM S, 1994, IEEE T IND APPL, V30, P1557